WARNING
Cassette type
Operation Condition
Heater off
Heater is off as shown in following diagram of heating
temperature.
Other than heating mode
Error occurred
Forced thermostat off
SW101
CN65
CN47
Duct type
DIP Switch 101-3 must be in the ON position when ducted electric heat application is be-
ing used. DIP switch 101-3 is set in the ON position by default from the factory. When DIP
switch 101-3 is in the ON position and ducted electric heat application is not being used, cold
draft occurs due to fan delay off operation.
Operation Condition
Heater off
DIP-SW101-3 On Heater is off as shown in following diagram of heating
temperature.
Other than heating mode
Error occurred
Forced thermostat off
Fan stop protection
Indoor unit fan
setting for
external heater
Enabled
DIP-SW101-3 Off Heater is off as shown in following diagram of heating
temperature.
Other than heating mode
Error occurred
Forced thermostat off
Indoor unit fan
setting for
external heater
Disabled
SW101
CN47
CN65
- 100 -
11-4. Details of function 11. External input and output (Compact cassette type and slim duct type indoor unit)
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type