12. Safety devices
Type of protection Protection form
Model
AOU45RLXFZ
Circuit protection
Current fuse
(PCB)
250 V, 10 A
250 V, 5 A
400 V, 5 A
250 V, 3.15 A
Protector
(PCB)
500 V, 45 A
Fan motor protection Thermal protection program
Activate
239±27 °F
(115±15 °C)
Fan motor stop
Reset
158 °F
(70 °C)
Fan motor restart
Compressor protection
Thermal protection program
(Compressor temp.)
Activate
226 °F
(108 °C)
Compressor stop
Reset
176 °F
(80 °C)
Compressor restart
Thermal protection program
(Discharge temp.)
Activate
230 °F
(110 °C)
Compressor stop
Reset
After 3 minutes
and 230 °F (110 °C) less than
Compressor restart