- 53 -
WALL MOUNTED
ASU30RLE
15) Server room control
Switches between normal control and server room control.
NOTE: To use this function, address setting of the primary unit and secondary unit needs to be
done.
When performing server room control, mind the followings:
Set to “01” on one of the 2 indoor units, and set to “02” on the other indoor unit.
As for the function details and setup procedure, refer to “Details of server room control” on page 4.
Function number Setting value Setting description Factory setting
96
00 Normal control
01 Server room control (Primary unit)
02 Server room control (Secondary unit)