Split system (Single phase and 3-phase type)
12 Maintenance Document 1544-1
Clear 5: Hydraulic Unit Heat exchanger thermistor error
Hydraulic Unit LED:
Green 4 flashes / Red 2 flashes
Outdoor Unit LED: 22 flashes
Probable causes:
Misconnection.
Sensor failure.
Interface PCB failure.
Check:
1. Check the sensor connection:
- See if the connector has been removed
- See if the connection is correct
- Check for any damage on the sensor cable.
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistance value.
Temperature (°C)
0 5 10 15 20 25 30 35 40 45 50
Resistance (k)
176 134 103 80,3 62,9 49,7 39,6 31,7 25,6 20,8 17,1
- If the thermistor is faulty, replace it.
OK
3. Check the electronic board voltage:
- Make sure circuit diagram of hydraulic unit and check terminal voltage at thermistor
(DC5.0V)
- If there is no voltage, replace Interface PCB.
OK