FT-C Vertical Electric Thermal Fluid Heater Manual 12 2013 ISSUE 1

!

 

 
 



1. Open the air bleed connection located directly over the pump shaft. Replace plug when a steady
stream of thermal uid, free of entrained air, ows from the port.
2. If ow has not started after two to ve minutes, remove the coupling guard and rotate the pump
shaft by hand in the proper direction. This should help move the cold viscous uid through close
tolerance seal areas. Replace plug when ow is steady.
3. If this fails to induce ow, introduce uid through the bleed port and rotate the shaft by hand to
work the uid around the seal area. Continue to add uid and rotate the shaft until no more uid
can be added.
4. Replace the plug and run pump for ve to ten seconds. Stop the pump, remove the plug and
wait for ow to start. If after two minutes ow has not started, add more uid as described above
and run the pump for ve minutes.
5. Constantly check the bearing area (located immediately behind the casing) for overheating.
Remove the plug and check for ow.
6. If ow has not started at this point, the uid may be too viscous to move through the seal area.
Start the system normally by selecting heat on the control panel, and raise the temperature
10°C. Continue to raise the system temperature by 10°C increments. Keep checking the pump
until ow starts.


1. Read manufacturers instruction manual thoroughly. If the pump is supplied by Fulton Ltd,
manufacturers literature is included in this manual.
 Do not run the pump before lling it with uid.
2. The pump should never be run without uid in the casing. For pumps equipped with mechanical
or air-cooled seals, air must be bled out of the stufng box area to ensure that thermal uid has
lubricated all seal and bearing areas. Operation of the pump even a short time without bleeding
rst will damage the pump.
3. Also use the thermal uid as a barrier uid. Remove the 3/8” plug at the barrier uid ll port. Fill
the cavity with thermal uid until it comes out of the overow tube. Replace the 3/8” plug.