FT-C Vertical Electric Thermal Fluid Heater Manual 12 2013 ISSUE 1



1. Maintenance of sufcient ow through the thermal uid heater and system at all times of
operation is critical. See table for recommended standard ow rates.
2. Note pressure gauge readings at start-up. Record readings in a log book and contact the Fulton
service department immediately in the event of abnormal readings. Failure to take action when
uid ow is reduced may result in serious and rapid degradation of the uid with possible
damage to the heater.





 11.4 1.7
 17 1.9
 22.7 1.4
 34 2.1
 56.8 1.7
 56.8 1.7
 85.2 1.8
 113.6 1.8
 139 1.2
 167 1.9
 182 1.9