EasyManua.ls Logo

FULTON FT-0800C - Schedule of Operator Tests and Checks

FULTON FT-0800C
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FT-C Vertical Electric Thermal Fluid Heater Manual 12 2013 ISSUE 1



The following schedule is the advice of Fulton Ltd. The frequency of tests and checks may vary
according to site risk assessment and/or specic requirements of the country/territory that the boiler
is installed in. Failure to maintain the heater adequately may void the Fulton warranty.
Maintenance on gas related parts of a boiler must be carried out by competent, trained personnel
vwho have the necessary equipment to check combustion. If any fault is found during these
operations, contact your Fulton representative.


1. Complete the log sheet attached at the end of this section at least once per day as a minimum.
It is recommended that the log sheet be lled out twice per shift of operation. The log sheet is
available from the Fulton service department and at the end of this manual.
2. Make a visual inspection of the entire system for leaks. Make repairs as soon as possible.
3. In systems utilising a water cooled thermal uid circulating pump, check the level of lubricating
oil in the self-levelling reservoir and check the cooling water circulation loop for proper
operation.
4. Note any failures on the ame programmer noting fault number, fault code, fault annunciation,
fault hour, fault cycle and fault time.
5. Check the exhaust for the presence of smoke. If smoke is present, contact your local Fulton
Representative.


 
1) Check inlet gas pressure at the beginning of the gas train. This should be accomplished by the
installation of an appropriately scaled gauge.
2) Check manifold gas pressure at high and low ! re and compare to Thermal Combustion Check
list lled out by start up technician. This should be accomplished by the installation of an
appropriately scaled gauge. Readings should be with .02” w.c. of Thermal Combustion
Checklist.

Table of Contents

Related product manuals