INSTALLATION 2
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-5
VSRT_IOM_2018-1213
Figure 2 - 10/15-HP Model VSRT Dimensions - Right
Side View (All dimensions in inches)
RIGHT SIDE VIEW
DRAWN BY:
CHECKED BY:
B.O.M. REVIEW: APPROVED BY:
ELECTRICAL REVIEW:
MECHANICAL REVIEW:
REVISIONDRAWING NUMBER
JOB NUMBER:
PROJECT NAME:
PROJECT MANAGER:
DESCRIPTION:
VSRT-10 GAS FIRED MODULATED STEAM BOILER
(150 PSI)
9-SR-010312 - PDS
-
T. KENNEDY
11/16/2017
N/A
N/A
W.W.
11/28/2017
N/A
E.B.W.
11/28/2017
This design and drawings are
proprietary and are the
exclusive property of The
Fulton Companies. The
corporation
does not permit
their use except with prior
written consent.
The items shown in this
drawing may be covered by
one or more patents of The
Fulton Companies.
SHEET 1 OF 1
THIRD ANGLE PROJECTION
TOLERANCES
FRACTION &
WHOLE VALUE
(1) PLACE DEC.
(2) PLACE DEC.
1/8
UNLESS OTHERWISE NOTED
DIMENSIONS ARE IN INCHES
0.03
(3) PLACE DEC.
SURFACE FINISH
250 MICRO-INCHES
0.005
0.5 DEGANGLE
0.015
Fulton Steam Solutions, Inc.
F
u
l
o
t
n
SEE
NOTE
9
SEE NOTES 3 AND 11
32 1/2 (MINIMUM WIDTH)
58 1/4
7 1/16
22 7/8
55 1/8
98 1/2
CLEARANCE REQUIRED
FOR BURNER REMOVAL
41 3/8
(AIR INLET)
73 5/8
(FUEL INLET)
(74)*
(STEAM OUTLET)
70
(MIN HEIGHT)
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
STEAM OUTP
UT LB/HR: FROM 0 PSIG AT 212°F (0 KG/CM² AT
100°C)
ALL CLEARA
NCES ARE FACTORY RECOMMENDATIONS. CONSULT
LOCAL JURIS
DICTION FOR EXACT CODE COMPLIANCE.
FULTON REC
OMMENDS MINIMUM CLEARANCE OF 36" IN FRONT
OF ELECTRIC
FULTON REC
OMMENDS 36" CLEARANCE BETWEEN INSPECTION
OPENINGS O
F ALL BOILERS, 18" CLEARANCE OF HANDHOLES,
AND 14" FRO
PLEASE REFE
R TO THE O&M MANUAL FOR ADDITIONAL
INFORMATIO
N REGARDING CLEARANCES AND INSTALLATION
INSTRUCTIO
ALL DIMENSI
ONS INSIDE ( ) DENOTE REFERENCE DIMENSIONS.
ALL DIMENSI
ONS INSIDE DENOTE OVERALL DIMENSIONS.
WE RESERVE
THE RIGHT TO CHANGE SPECIFICATIONS
AND/OR DIM
ENSIONS. ALL INFORMATION IS SUBJECT
TO CHANGE
BASED ON ADDITION OF ANY OPTIONAL
EQUIPMENT
AND/OR ACCESSORIES. PLEASE CONSULT THE
FACTORY FO
R PROJECT SPECIFIC ESTIMATES IF
ADDITIONAL
OPTIONS OR ACCESSORIES ARE REQUIRED.
RECOMMEN
DED STACK RUN IS MINIMUM 24" STRAIGHT OFF
THE REAR O
F THE BOILER, PRIOR TO MAKING A
DIRECTION
LOCAL COD
ES CAN SUPERCEDE FULTON RECOMMENDED
CLEARANCE.
*SIZE DEPE
NDS ON TRIM PRESSURE.
MAX ALLOWABLE WORKING PRESSURE:
BOILER OUTPUT:
MINIMUM INCOMING GAS PRESS
URE:
150 PSI
335,000 BTU/HR
345 LBS/HR
54.5 SQ. FT.
94 GAL.
1,932 LBS.
2,716 LBS.
2,500 LBS.
EQUIPMENT SPECIFICATION CHART
APPROXIMATE FLOODED WEIGH
MINIMUM DRAFT REQUIREMENT:
BURNER TURNDOWN:
APPROXIMATE SHIPPING WEIGH
APPROXIMATE OPERATING WEIG
APPROXIMATE DRY WEIGHT:
WATER CAPACITY (OPERATING):
NET EFFECTIVE HEATING SURFACE:
STEAM OUTPUT/MIN. SRV CAPACITY:
400 CU FT/HR
BOILER INPUT:
3" W.C.
BOILER INPUT: (NATURAL GAS)
400,000 BTU/HR
CUSTOMER CONNECTIONS
ITEM DESCRIPTION SIZE TYPE
A FEED WATER INLET 1" N.P.T.
B BLOWDOWN OUTLET 1" N.P.T.
C STEAM OUTLET*
1 1/4"
N.P.T.
D EXHAUST STACK
6"
- - -
E
SAFETY RELIEF VALVE* 1"
N.P.T.
F
FUEL INLET
1" N.P.T.
G WATER COLUMN DRAIN 1" N.P.T.
H SIGHT GLASS DRAIN
1/4"
N.
P.T.
J WATER SAMPLE PORT
1/4"
N.P.T.
K STEAM SAMPLE PORT
1/4"
N.P.T.
L
SURFACE BLOWDOWN (PLUGGED) 3/4"
N.P.T.
M
HIGH WATER PROTECTION (CAPPED)
3/4"
N.P.T.
N SINGLE SOURCE POWER
- - -
N.P.T.
P COMBUSTION AIR INLET
6"
- - -
R
AUXILIARY WATER COLUMN (CAPPED)
1"
N.P.T.
5
(BOTTOM BLOWDOWN)
22 3/8
(FEEDWATER)
71 5/8( *)
(S.R.V.)
76 3/8*
43 1/16
(EXHAUST STACK)
-
INITIAL RELEASE
- - - - -
REVISION HISTORY
REV REVISION DESCRIPTION B.O.M. ELEC. ENG. MECH. ENG CHECKED APPROVED
NOTE: OPERATING FULL LOAD AMPERAGE (FLA)
REFERS TO THE BOILER'S RATED CURRENT DRAW
AT HIGH FIRE.
ELECTRICAL REQUIREMENTS
VOLTAGE OPERATING FLA
120/1/60
10 AMPS
E
C
P
F
B
A
L
R
D
M