GALaxy eHydro Elevator Controller Section 6 – Main CPU Faults & Detailed Faults
6-55
Table 6-0: Main CPU Faults
Possible Cause/Suggested Fix
Emergency Power
Recall Car Out of
Service Car 7. Car 7
was out of service
while elevators were
in
an Emergency Power
Recall Sequence.
Emergency Power
Recall Car Out of
Service Car 8. Car 8
was out of service
while elevators were
in an Emergency
Power Recall
Sequence.
Emergency Power
Recall Time-out Car 1.
Car 1 timeout while it
was in Emergency
power recall mode.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor•
Verify the speed of the car during recovery operation.
Emergency Power
Recall Time-out Car 2.
Car 2 timeout while it
was in Emergency
power recall mode.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify the speed of the car during recovery operation.
Emergency Power
Recall Time-out Car 3.
Car 3 timeout while it
was in Emergency
power recall mode.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify the speed of the car during recovery operation.
Emergency Power
Recall Time-out Car 4.
Car 4 timeout while it
was in Emergency
power recall mode.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify the speed of the car during recovery operation.