GALaxy eHydro Elevator Controller Section 4 - Troubleshooting
4-3
4.5 The Safety PAL Functions
The Safety PAL monitors the Main CPU RUN and Door Zone outputs, the NTS Terminal Limit and Door
Zone outputs, car Inspection and Door Gate/Lock inputs, and the speed outputs from both the Main
CPU and the NTS. The Safety PAL’s job is to interrupt or prevent a run operation in case of an unsafe
conditions.
Run Control - CPU Control outputs gated by Safety PAL:
SD – Solenoid Down Command
MC1 – Dual Motor Contactor
SUF – Solenoid Up Fast Command
STE – Soft-Starter Enable
SDF – Solenoid Down Fast Command
Door Zone Status – CPU Control and NTS MCU Control UL – Up Level
DL – Down Level
DZ – Door Zone
SEL_OK – Communications to Selector OK and no Selector Fault
SPD150 – Speed greater than 150 fpm
SPD75 – Speed greater than 75 fpm
GS – Car Gate Switch or Lock
RGS – Rear Gate Switch or Lock
GBP – Gate Bypass
LBP – Lock Bypass
Inspection Status & Control:
AUTO– Automatic Operation
IU – Car Top Inspection Up
ID – Car Top Inspection Down
MRIN – Motor Room Inspection
MRIU – Motor Room Inspection
UP
BAU – Bottom Access Up
BAD – Bottom Access Down
MRID – Motor Room Inspection
Down
Terminal Limit Status – NTS MCU Control outputs gated by Safety PAL:
UN – Up Normal Limit
UT – Up Terminal Slowdown
DN – Down Normal Limit
DT – Down Terminal Slowdown
Figure 4-1 illustrates all the Main CPU, NTS Processor and Safety PAL functions: