GALaxy eHydro Elevator Controller Section 4 - Troubleshooting
4-3
4.5 The Safety PAL Functions
The Safety PAL monitors the Main CPU RUN and Door Zone outputs, the NTS Terminal Limit and Door
Zone outputs, car Inspection and Door Gate/Lock inputs, and the speed outputs from both the Main
CPU and the NTS. The Safety PAL’s job is to interrupt or prevent a run operation in case of an unsafe
conditions.
Run Control - CPU Control outputs gated by Safety PAL:
SU Solenoid Up Command
MC Motor Contactor
SD Solenoid Down Command
MC1 Dual Motor Contactor
SUF Solenoid Up Fast Command
STE Soft-Starter Enable
SDF Solenoid Down Fast Command
RUN Run Relay Command
Door Zone Status CPU Control and NTS MCU Control UL Up Level
DL Down Level
DZ Door Zone
SEL_OK Communications to Selector OK and no Selector Fault
SPD150 Speed greater than 150 fpm
SPD75 Speed greater than 75 fpm
Door Status:
DLT Door Lock Top
GS Car Gate Switch or Lock
DLM Door Lock Middle
RLM Rear Lock Middle
DLB Door Lock Bottom
RGS Rear Gate Switch or Lock
GBP Gate Bypass
LBP Lock Bypass
Inspection Status & Control:
GLB Gate/Lock Bypass
AUTO Automatic Operation
INS Car Top Inspection
ICI In Car Inspection
IU Car Top Inspection Up
ACC Access
ID Car Top Inspection Down
TAU Top Access Up
MRIN Motor Room Inspection
TAD Top Access Down
MRIU Motor Room Inspection
UP
BAU Bottom Access Up
BAD Bottom Access Down
MRID Motor Room Inspection
Down
Terminal Limit Status NTS MCU Control outputs gated by Safety PAL:
UN Up Normal Limit
UT Up Terminal Slowdown
DN Down Normal Limit
DT Down Terminal Slowdown
Figure 4-1 illustrates all the Main CPU, NTS Processor and Safety PAL functions: