GALaxy eHydro Elevator Controller Section 6 Main CPU Faults & Detailed Faults
6-87
Table 6-2: Faults from the Hall Call Driver Board Devices on the GRCAN Serial Port
Fault
Description
Possible Cause/Suggested Fix
Ax Dn In Ovld
HCB Aux Down input
overload
• Controller detected overload in the input from the Aux terminal
at the station. To identify fault device refer to Detailed Fault Log
'dev' and 'dv2' will provide address for Serial Driver address and
Station where the fault was generated.
Ax Up In Ovld
HCB Aux Up input
overload
• Controller detected overload in the input from the Aux terminal
at the station. To identify fault device refer to Detailed Fault Log
'dev' and 'dv2' will provide address for Serial Driver address and
Station where the fault was generated.
Dev Comm
Loss
The Driver does not
see this HCB device
• Comm faults above and below a device check wiring
• Board not powering up check 24VAC and MCU on device
• Fuses blown on driver
Dev Comm
Loss
The Driver does not
see this HCB device
• Comm faults above and below a device check wiring
• Board not powering up check 24VAC and MCU on device
• Fuses blown on driver
Device Reset
The HCB has just
comeback online
• Fixed previous problem.
There is a power/communication problem, where the board is
either resetting (power) or temporarily losing communication on
both ports.
Device Reset
The HCB has just
comeback online
• Fixed previous problem.
There is a power/communication problem, where the board is
either resetting (power) or temporarily losing communication on
both ports.
Dn FET Open
HCB fet open down
• Replace GALX-1054AN
Dn FET Open
HCB fet open down
• Replace GALX-1054AN
Dn FET Short
HCB fet short down
• Replace GALX-1054AN
Dn FET Short
HCB fet short down
• Replace GALX-1054AN