GALaxy eHydro Elevator Controller Section 7 Main CPU Adjustable Variables
7-12
Table 7-3: Car Options
Field Variable
Min
Max
Initial
Units
NCU Lant Ctrl
0
3
0
-
Next Up Direction Lantern Control.
+1 = Turn off hall lantern after next up time.
+2 = Turn off cab lantern after next up time.
NCU Pref Ctrl
0
1
0
-
Next Up Preference Control. When set allows
direction preference to change before the door starts
to close after the next up door time.
NoHC Dor
Reop
0
3
0
-
No Hall Call Button Door Reopen. When set do not
reopen the door from an at floor hall call.
Non-Simul Dor
0
2
0
-
Non-Simultaneous Doors.
0 = Both front and rear doors will open at the same
time if there is a demand at both the front and rear
openings.
1 = The front doors will open first before the rear
doors open if there is a demand to open.
2 = The rear doors will open first before the front
doors open if there is a demand to open.
Nudg No Calls
0
1
0
-
Nudge with No Calls. If set the doors will close on
nudging even if the elevator has no onward calls.
Nudge Dis Ctl
0
7
0
-
Nudging Disable Control.
+1 = Do not turn on the NUD output when doors are
in nudging close mode, basically you are disabling
nudging output.
+2 = When doors are in nudging close mode and SE
input is ON, keep doors open and also keep FB/NB
output latched.
+4 = Sound the nudging buzzer but do not close the
doors on nudging.