GALaxy eHydro Elevator Controller Section 7 – Main CPU Adjustable Variables
7-25
Table 7-5: Emergency Services
Hospital Service Close door Car Call. Close the
doors from a car call when the car is on Hospital
Service.
Fire Service Hoistway HWS2 Sensor Location .
0 = Same HW
1 = Separate hoistway
Second Hoistway Fire Service Sensor Return
Option.
0 = Main recall floor
1 = Alternate recall floor.
Machine Room Fire Sensor Return Floor Selection.
0 = Return to the Main fire floor,
1 = Return to the Alternate fire floor.
Medical Service Override Car Call Security.
1 = Medical service car will override car call security.
Medical Emergency Return floor.
Medical Emergency Switch Location. Selects the
switch location for the front or rear door.
0 = Front
1 = Rear
Medical service Door Reopen. When car is on
medical Service, this parameter determines the
door open sequence for re-open:
0 = Stop,
1 = Constant pressure,
2 = Momentary to DOL
Medical Service Overrides Independent Control:
0 = Immediate,
1 = After Delay,
2 = No override