GALaxy eHydro Elevator Controller Section 7 Main CPU Adjustable Variables
7-25
Table 7-5: Emergency Services
Field Variable
Min
Max
Initial
Units
HSV DoorCl CC
0
1
0
-
Hospital Service Close door Car Call. Close the
doors from a car call when the car is on Hospital
Service.
HWS2 Fire Loc
0
1
50
-
Fire Service Hoistway HWS2 Sensor Location .
0 = Same HW
1 = Separate hoistway
HWS2 Fire Ret
0
1
0
-
Second Hoistway Fire Service Sensor Return
Option.
0 = Main recall floor
1 = Alternate recall floor.
MachRm FirRet
0
1
0
-
Machine Room Fire Sensor Return Floor Selection.
0 = Return to the Main fire floor,
1 = Return to the Alternate fire floor.
Med CCS Ovrrd
0
1
0
-
Medical Service Override Car Call Security.
1 = Medical service car will override car call security.
Med Em Floor
Bottom
Floor
Top
Floor
1
floor
Medical Emergency Return floor.
Med Em Sw Loc
0
1
0
-
Medical Emergency Switch Location. Selects the
switch location for the front or rear door.
0 = Front
1 = Rear
MedDoorReopen
0
2
0
-
Medical service Door Reopen. When car is on
medical Service, this parameter determines the
door open sequence for re-open:
0 = Stop,
1 = Constant pressure,
2 = Momentary to DOL
MedInd Ovrrid
0
2
0
-
Medical Service Overrides Independent Control:
0 = Immediate,
1 = After Delay,
2 = No override