GALaxy eHydro Elevator Controller Section 7 Main CPU Adjustable Variables
7-29
Table 7-6: Group Dispatch
Field Variable
Min
Max
Initial
Lobby Request
0
Number
Cars
0
Lobby Request. Number of Cars Requested to the
Lobby floor. Used with Next Car Up operation.
Next Car Up
0
7
0
Next Car Up. Set to 1 or 2 will activate the Next Car
Up operation.
1 = The next up car will open its door at the lobby and
keep it open. The car is allowed to leave the floor
after the Lobby Dwell time expires but will remain at
the floor with the door open until an onward call is
assigned to it.
2 = The next up car will close its door after the Lobby
Dwell time expires and go off of next up but will
remain at the lobby. An up hall call at the lobby will
cause the car to open its door and go on next up.
4 = Next up is activated on Up Peak detection only.
Next up can also be activated from an input.
Park Dly Time
0
120
8
Parking Delay Time. Time delay an idle car waits
before being parked.
Parking
0
Number
Cars
1
Number of Cars to Park. One car is parked at the
lobby. The remaining cars are parked at the most
used floors of the building. If set to zero, no cars are
parked.
Parking Flr 1
0
Top
Floor
0
Parking Floor 1. Floor to park the idle car. If set to
zero, the group will use number of hall call history to
decide where to park the car. The parking variable
must be set to at least 1 for this function to work. See
also Parking Type.
Parking Flr 2
0
Top
Floor
0
Parking Floor 2. Floor to park the idle car. If set to
zero, the group will use number of hall call history to
decide where to park the car. The parking variable
must be set to at least 1 for this function to work. See
also Parking Type.