GALaxy eHydro Elevator Controller Section 7 Main CPU Adjustable Variables
7-38
Table 7-7: Group Options
Field Variable
Min
Max
Initial
Units
Description
Recall Timout
1
600
60
Sec
Recall Time-out. The time allowed for the car to
reach the recall floor during the emergency power
recall sequence. If this timer expires, the next car is
selected to recall.
Sabb Restart
0
3200
8
Sec
Sabbath Restart Delay Time. The amount of time
after the elevator answered the last sabbath call to
restart the process.
Single AutoPB
0
5
0
-
Single Automatic Push Button Operation.
0 = Manual Doors (this would be the normal
operation for cars with manual doors).
1 = Enable SAPB operation for simplex car with
automatic doors.
2 = Disable SAPB operation for cars with manual
doors.
3 = Invalid setting.
4 = Allow only one car call to be entered at floor for
cars with manual doors regardless of the door
position.
5 = Allow only one car call to be entered at floor for
cars with automatic doors. This feature normally
allows only hall calls and car calls to register when
the doors are closed.
SkpCar@RcFLD
O
0
1
0
-
Skip Car at Recall Floor with Door Open. While on
Emergency Power Recall sequence: if enabled, out of
service cars at the Emergency Power Recall floor with
door open will be given a chance to run,
0 = Override immediately
1 = Override after timedelay. Time delay defined by
variable 'EP Recover Tim'.
SkpCarN@RcF
DO
0
1
0
-
Skip Car Not at Recall Floor with Door Open. While
on Emergency Power Recall sequence: if enabled, out
of service cars at the Emergency Power Recall floor
with door open will be given a chance to run,
0 = Override immediately
1 = Override after timedelay. Time delay defined by
variable 'EP Recover Tim'.