Illustration 7.14: Cable entry holes for unit size 21. The sugges-
ted use of the holes are purely recommendations and other
solutions are possible.
Illustration 7.15: Cable entry holes for unit size 22. The sugges-
ted use of the holes are purely recommendations and other
solutions are possible.
Illustration 7.16: Cable entry holes for unit size 31. The sugges-
ted use of the holes are purely recommendations and other
solutions are possible.
Illustration 7.17: Cable entry holes for unit size 32. The sugges-
ted use of the holes are purely recommendations and other
solutions are possible.
Term. no. 96 97 98 99
U V W
PE
1)
Motor voltage 0-100% of mains voltage.
3 wires out of motor
U1 V1 W1
PE
1)
Delta-connected
W2 U2 V2 6 wires out of motor
U1 V1 W1
PE
1)
Star-connected U2, V2, W2
U2, V2 and W2 to be interconnected separately.
1)
Protected Earth Connection
AF-650 GP Design Guide
123