4.3 Electrical Data - 380-480 V
Mains Supply 3 x 380 - 480 VAC
AF-650 GP
Typical Shaft Output [kW]
0.37 0.75 1.5 2.2 3 4 5.5 7.5
Typical Shaft Output [HP] at 460V 0.5 1.0 2.0 3.0 4.0 5.0 7.5 10
Unit Size IP20/IP21 12 12 12 12 12 12 13 13
Unit Size IP55, 66 15 15 15 15 15 15 15 15
Output current
Heavy duty (HD) 160% for 1 minute
Shaft output [kW] 0.37 0.75 1.5 2.2 3 4 5.5 7.5
Continuous
(3 x 380-440 V) [A]
1.3 2.4 4.1 5.6 7.2 10 13 16
Intermittent
(3 x 380-440 V) [A]
2.1 3.8 6.6 9.0 11.5 16 20.8 25.6
Continuous
(3 x 441-480 V) [A]
1.2 2.1 3.4 4.8 6.3 8.2 11 14.5
Intermittent
(3 x 441-480 V) [A]
1.9 3.4 5.4 7.7 10.1 13.1 17.6 23.2
Continuous KVA
(400 V AC) [KVA]
0.9 1.7 2.8 3.9 5.0 6.9 9.0 11.0
Continuous KVA
(460 V AC) [KVA]
0.9 1.7 2.7 3.8 5.0 6.5 8.8 11.6
Max. cable size
(mains, motor, brake)
[AWG]
2)
[mm
2
]
24 - 10 AWG
0.2 - 4 mm
2
24 - 10 AWG
0.2 - 4 mm
2
Max. input current
Continuous
(3 x 380-440 V ) [A]
1.2 2.2 3.7 5.0 6.5 9.0 11.7 14.4
Intermittent
(3 x 380-440 V ) [A]
1.9 3.5 5.9 8.0 10.4 14.4 18.7 23.0
Continuous
(3 x 441-480 V) [A]
1.0 1.9 3.1 4.3 5.7 7.4 9.9 13.0
Intermittent
(3 x 441-480 V) [A]
1.6 3.0 5.0 6.9 9.1 11.8 15.8 20.8
Max. mains fuses
1)
[A]
10 10 10 20 20 20 32 32
Environment
Estimated power loss
at rated max. load [W]
4)
35 46 62 88 116 124 187 255
Weight,
Unit Size IP20
4.7 4.8 4.9 4.9 4.9 4.9 6.6 6.6
Unit Size IP55, 66 13.5 13.5 13.5 13.5 13.5 13.5 14.2 14.2
Efficiency
4)
0.93 0.96 0.97 0.97 0.97 0.97 0.97 0.97
0.37 - 7.5 kW only available as 160% heavy duty (HD).
AF-650 GP Design Guide
55
4