4.4 Electrical Data - 525-600 V
Mains Supply 3 x 525 - 600 VAC
AF-650 GP
Typical Shaft Output [kW] 0.75 1.5 2.2 3 4 5.5 7.5
Typical Shaft Output [HP] at 575V 1.0 2.0 3.0 4.0 5.0 7.5 10
Unit Size IP20 13 13 13 13 13 13 13
Unit Size IP55 15 15 15 15 15 15 15
Output current
Continuous
(3 x 525-550 V ) [A]
1.8 2.9 4.1 5.2 6.4 9.5 11.5
Intermittent
(3 x 525-550 V ) [A]
2.9 4.6 6.6 8.3 10.2 15.2 18.4
Continuous
(3 x 551-600 V ) [A]
1.7 2.7 3.9 4.9 6.1 9.0 11.0
Intermittent
(3 x 551-600 V ) [A]
2.7 4.3 6.2 7.8 9.8 14.4 17.6
Continuous kVA (525 V AC) [kVA] 1.7 2.8 3.9 5.0 6.1 9.0 11.0
Continuous kVA (575 V AC) [kVA] 1.7 2.7 3.9 4.9 6.1 9.0 11.0
Max. cable size
(mains, motor, brake)
[AWG]
2)
[mm
2
]
24 - 10 AWG
0.2 - 4 mm
2
24 - 10 AWG
0.2 - 4 mm
2
Max. input current
Continuous
(3 x 525-600 V ) [A]
1.7 2.7 4.1 5.2 5.8 8.6 10.4
Intermittent
(3 x 525-600 V ) [A]
2.7 4.3 6.6 8.3 9.3 13.8 16.6
Max. mains fuses
1)
[A]
10 10 20 20 20 32 32
Environment
Estimated power loss
at rated max. load [W]
4)
35 65 92 122 145 195 261
Weight,
Unit Size IP20 [kg]
6.5 6.5 6.5 6.5 6.5 6.6 6.6
Weight,
Unit Size IP55, 66 [kg]
13.5 13.5 13.5 13.5 13.5 14.2 14.2
Efficiency
4)
0.97 0.97 0.97 0.97 0.97 0.97 0.97
AF-650 GP Design Guide
61
4