3.5.2 EMC Test Results
The following test results have been obtained using a system with a frequency converter (with options if relevant), a screened control cable, a control box
with potentiometer, as well as a motor and motor screened cable.
RFI filter type Conducted emission Radiated emission
Standards and requirements EN 55011 Class B
Housing, trades
and light indus-
tries
Class A
Group 1
Industrial en-
vironment
Class A Group 2
Industrial envi-
ronment
Class B
Housing, trades
and light indus-
tries
Class A Group 1
Industrial environ-
ment
EN/IEC 61800-3 Category C1
First environ-
ment Home
and office
Category C2
First environ-
ment Home
and office
Category C3
Second envi-
ronment Indus-
trial
Category C1
First environment
Home and office
Category C2
First environment
Home and office
With RFI
AF-650 GP:
0-37 kW 200-240 V 50 m 150 m 150 m No Yes
0-75 kW 380-480 V 50 m 150 m 150 m No Yes
No RFI obtain Class A2
AF-650 GP
0-3.7 kW 200-240 V No No 5 m No No
5.5-37 kW 200-240 V No No 25 m No No
0-7.5 kW 380-480 V No No 5 m No No
11-75 kW 380-480 V No No 25 m No No
90-800 kW 380-480 V No No 150 m No No
90-1000 kW 525-690 V No No 150 m No No
11-22 kW 525-690 V
1)
No No 25 m No No
30-75 kW 525-690 V
2)
No No 25 m No No
With RFI
AF-650 GP
90-800 kW 380-480 V No 150 m 150 m No Yes
11-22 kW 525-690 V
1)
No 100 m 100 m No Yes
30-75 kW 525-690 V
2)
No 150 m 150 m No Yes
90-315 kW 525-690 V No 30 m 150 m No No
No RFI
AF-650 GP
0.75-75 kW 525-600 V - - - - -
Table 3.1: EMC Test Results (Emission, Immunity)
1) Frame size 2X
2) Frame size 3X
AF-650 GP Design Guide