EasyManua.ls Logo

GE AF-650 GP - Introduction to Test Procedures; Tools Required for Testing

GE AF-650 GP
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.6 General Specifications
Mains supply (L1, L2, L3):
Supply voltage 200-240 V ±10%
Supply voltage 380-480 V ±10%
Supply voltage 525-690 V ±10%
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the AF-650 GP continues until the intermediate circuit voltage drops below the minimum stop level, which corresponds
typically to 15% below the frequency converter's lowest rated supply voltage. Power-up and full torque cannot be expected at mains voltage lower than 10%
below the frequency converter's lowest rated supply voltage.
Supply frequency
50/60 Hz ±5%
Max. imbalance temporary between mains phases 3.0 % of rated supply voltage
True Power Factor () 0.9 nominal at rated load
Displacement Power Factor (cos ϕ) near unity (> 0.98)
Switching on input supply L1, L2, L3 (power-ups) 7.5 kW maximum 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) 11-75 kW maximum 1 time/min.
Switching on input supply L1, L2, L3 (power-ups) 90 kW maximum 1 time/2 min.
Environment according to EN60664-1 overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/480/600/ 690 V maximum.
Motor output (U, V, W):
Output voltage 0 - 100% of supply voltage
Output frequency (0.25-75 kW) 0 - 1000 Hz
Output frequency (90-1000 kW) 0 - 800* Hz
Output frequency in Flux Mode 0 - 300 Hz
Switching on output Unlimited
Ramp times 0.01 - 3600 sec.
* Voltage and power dependent
Torque characteristics:
Starting torque (Constant torque) maximum 160% for 60 sec.
*
Starting torque maximum 180% up to 0.5 sec.
*
Overload torque (Constant torque) maximum 160% for 60 sec.
*
Starting torque (Variable torque) maximum 110% for 60 sec.
*
Overload torque (Variable torque) maximum 110% for 60 sec.
*Percentage relates to the nominal torque.
Cable lengths and cross sections for control cables*:
Max. motor cable length, screened 150 m
Max. motor cable length, unscreened 300 m
Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves 1.5 mm
2
/16 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves 1 mm
2
/18 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar 0.5 mm
2
/20 AWG
Minimum cross section to control terminals 0.25 mm
2
/ 24 AWG
* Power cables, see tables in section “Electrical Data” of the AF-650 GP Design Guide
AF-650 GP Design Guide
71
4

Table of Contents

Other manuals for GE AF-650 GP

Related product manuals