10.10.5 Control Word according to PROFIdrive Profile (CTW)
The Control word is used to send commands from a master (e.g. a PC) to a
slave.
Bit
Bit = 0 Bit = 1
00 OFF 1 ON 1
01 OFF 2 ON 2
02 OFF 3 ON 3
03 Coasting No coasting
04 Quick stop Accel/Decel
05 Hold frequency output Use Accel/Decel
06 Accel/Decel stop Start
07 No function Reset
08 Jog 1 OFF Jog 1 ON
09 Jog 2 OFF Jog 2 ON
10 Data invalid Data valid
11 No function Slow down
12 No function Catch up
13 Parameter set-up Selection lsb
14 Parameter set-up Selection msb
15 No function Reverse
Explanation of the Control Bits
Bit 00, OFF 1/ON 1
Normal ramp stop using the ramp times of the actual selected ramp.
Bit 00 = "0" leads to the stop and activation of the output relay 1 or 2 if the output frequency is 0 Hz and if [Relay 123] has been selected in par. E-24 Function
Relay.
When bit 00 = "1", the frequency converter is in State 1: “Switching on inhibited”.
Please refer to the PROFIdrive State Transition Diagram, at the end of this section.
Bit 01, OFF 2/ON 2
Coasting stop
When bit 01 = "0", a coasting stop and activation of the output relay 1 or 2 occurs if the output frequency is 0 Hz and if [Relay 123] has been selected in
par. E-24 Function Relay.
When bit 01 = "1", the frequency converter is in State 1: “Switching on inhibited”. Please refer to the PROFIdrive State Transition Diagram, at the end of this section.
Bit 02, OFF 3/ON 3
Quick stop using the ramp time of par. C-23 Quick Stop Decel Time. When bit 02 = "0", a quick stop and activation of the output relay 1 or 2 occurs if the output
frequency is 0 Hz and if [Relay 123] has been selected in par. E-24 Function Relay.
When bit 02 = "1", the frequency converter is in State 1: “Switching on inhibited”.
Please refer to the PROFIdrive State Transition Diagram, at the end of this section.
Bit 03, Coasting/No coasting
Coasting stop Bit 03 = "0" leads to a stop. When bit 03 = "1", the frequency converter can start if the other start conditions are satisfied.
NB!
The selection in par. O-50 Coasting Select Coasting select determines how bit 03 is linked with the corresponding function of the digital inputs.
Bit 04, Quick stop/Accel/Decel
Quick stop using the ramp time of par. C-23 Quick Stop Decel Time.
When bit 04 = "0", a quick stop occurs.
When bit 04 = "1", the frequency converter can start if the other start conditions are satisfied.
NB!
The selection in par. O-51 Quick Stop Select determines how bit 04 is linked with the corresponding function of the digital inputs.