Mains Supply 3 x 380 - 480 VAC
AF-650 GP 40 HP 50 HP 60 HP 75 HP 100 HP
High/ Normal Load*
HD LD HD LD HD LD HD LD HD LD
Typical Shaft output
[kW]
30 37 37 45 45 55 55 75 75 90
Typical Shaft Output [HP]
at 460V
40 50 50 60 60 75 75 100 100 120
Unit Size IP20 24 33 33 34 34
Unit Size IP55, 66 31 31 31 32 32
Output current
Continuous
(3 x 380-440 V) [A]
61 73 73 90 90 106 106 147 147 177
Intermittent (60 sec
overload)
(3 x 380-440 V) [A]
91.5 80.3 110 99 135 117 159 162 221 195
Continuous
(3 x 441-480 V) [A]
52 65 65 80 80 105 105 130 130 160
Intermittent (60 sec
overload)
(3 x 441-480 V) [A]
78 71.5 97.5 88 120 116 158 143 195 176
Continuous KVA
(400 V AC) [KVA]
42.3 50.6 50.6 62.4 62.4 73.4 73.4 102 102 123
Continuous KVA
(460 V AC) [KVA]
51.8 63.7 83.7 104 128
Max. input current
Continuous
(3 x 380-440 V ) [A]
55 66 66 82 82 96 96 133 133 161
Intermittent (60 sec
overload)
(3 x 380-440 V ) [A]
82.5 72.6 99 90.2 123 106 144 146 200 177
Continuous
(3 x 441-480 V) [A]
47 59 59 73 73 95 95 118 118 145
Intermittent (60 sec
overload)
(3 x 441-480 V) [A]
70.5 64.9 88.5 80.3 110 105 143 130 177 160
Max. cable size IP20,
mains and motor [mm
2
(AWG
2)
)]
35 (2) 50 (1) 50 (1) 95 (4/0) 150 (300mcm)
Max. cable size IP20,
load share and brake
[mm
2
(AWG
2)
)]
35 (2) 50 (1) 50 (1) 95 (4/0) 95 (4/0)
Max. cable size,
IP21/55/66 [mm
2
(AWG
2)
)]
90 (3/0) 90 (3/0) 90 (3/0) 120 (4/0) 120 (4/0)
Max cable size with
mains disconnect
35 (2) 70 (3/0) 150 (300mcm)
Max. mains fuses [A]
1
100 125 160 250 250
Estimated power loss
at rated max. load [W]
4)
570 698 697 843 891 1083 1022 1384 1232 1474
Weight,
Unit SizeIP 55, 66 [kg]
45 45 45 65 65
Efficiency
4)
0.98 0.98 0.98 0.98 0.99
* Heavy duty (HD) = 160% torque during 60 s, Light duty (LD) = 110% torque during 60 s
AF-650 GP Design Guide
57
4