Control card performance:
Scan interval AF-650 GP: 1 ms
Surroundings:
Unit Size 12, 13 and 15 (see 3.1 Product Overview for power ratings) IP 20, IP 55, IP 66
Unit Size 21, 22, 31 and 32 IP 21, IP 55, IP 66
Unit Size 23, 24, 33 and 34 IP 20
Unit Size 41, 42 , 51, 61, 62, 63 and 64 IP 21, IP 54
Unit Size 43, 44 and 52 IP 00
Unit Size kit available 7.5 kW IP21/TYPE 1/IP 4X top
Vibration test, Unit Size 1x, 2x and 3x 1.0 g RMS
Vibration test, Unit Size 4x, 5x and 6x 0.7 g
Max. relative humidity 5% - 95%(IEC 60 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class Kd
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature, Unit Size 1x, 2x and 3x Max. 50 °C (24-hour average maximum 45 °C)
Ambient temperature, Unit Size 4x, 5x and 6x Max. 45 °C (24-hour average maximum 40 °C)
Derating for high ambient temperature, see section on special conditions
Minimum ambient temperature during full-scale operation
0 °C
Minimum ambient temperature at reduced performance - 10 °C
Temperature during storage/transport -25 - +65/70 °C
Maximum altitude above sea level 1000 m
Derating for high altitude, see section on special conditions
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions
Control card, USB serial communication:
USB standard 1.1 (Full speed)
USB plug USB type B “device” plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is
not galvanically isolated from protection earth. Use only an isolated laptop as PC connection to the USB connector on the frequency
converter.
AF-650 GP Design Guide