106 • Appendix B - Profibus
B.5. Setting Parameters Registers for Data Request
Parameter # Range Default
Main Parameters
Starter Current 0 8..1400 58 (Amp.)
Motor Current 1 4..1750 58 (Amp.)
Line/Delta Configuration 2 0 (Line), 1 (Inside Delta) 0 (Line)
Undercurrent_FLT 3 0..90 (% of FLA) 0 (% of FLA)
Undercurrent_DLY 4 1..40 10 (Seconds)
O/C JAM Fault 5 200..850 (% of FLA) 850 (% of FLA)
O/C JAM Delay 6 0..50 5 (0.5 Sec.)
Overload_Class 7 75..150 115 (% of FLA)
Overload_Protect 8 1..10 4 (Seconds)
Undervoltage_FLT 9 120..600 300 (Volt)
UnderVoltage_DLY 10 1..10 5 (Seconds)
Overvoltage_FLT 11 150..750 480 (Volt)
Overvoltage_DLY 12 1..10 2 (Seconds)
Reserved 14..23
Start Settings
Soft Start Curve 24 0..10 (5..9 are reserved) 0 (Standard).
Kickstart Time 25 0..10 (Tenth Seconds) 0 (No Pulse)
Starting Voltage/Current 26 10..80 30 (% of full
voltage)
Current Limit 27 100..500 400 (% of FLA)
Ramp UP Time 28 1..90 10 (Seconds)
Max. Start Time 29 1..250 30 (Seconds)
Number of Starts 30 1..10 & (11 = OFF) 10
Duty Cycle Time 31 1..60 30 (Minutes)
Start_Lockout 32 1..60 15 (Minutes)
EOR Relay Delay 33 0..40 5 (Seconds)
Reserved 35..39
Stop Settings
Soft Stop Curve 40 0..10 (5..9 are reserved) 0 (Standard)
Ramp DOWN Time 41 1..30 10 (Seconds)
End Torque 42 0..10 0 (Minimum)
Reserved 43..47
Dual Settings
Starting VOLT-2 48 10..80 % of full voltage 30
Current Limit-2 49 100..500 400 % of FLA
Ramp UP-2 50 1..90 10 (Seconds)
Ramp DOWN-2 51 1..30 10 (Seconds)
Motor Current-2 52 5..1400 31 (Amp.)
Reserved 53..55
Slow SP & Saving Parameters
Energy Saving 56 1..10 0
Slow Sp eed TRQ. 57 1..10 8
Max_Slow_SP_Time 58 1..250 30 (Seconds)
Reserved 59..62
Fault Settings
Phase Loss 63 0..1 0 (No)
Phase Sequence 64 0..1 0 (No)
Auto Reset 65 0 / 1 (0 - No, 1 - Yes) 1 (No)