Chapter 1. Installation
2 DigitalFlow™ GF868 Startup Guide (1 and 2-Channel)
1.3 Site Considerations 
Since the relative physical locations of the flowcell(s) and the GF868 electronics are important, use the guidelines 
given in this section when planning your GF868 system installation. 
1.3.1 Electronics Console Location 
Normally, the GF868 electronics enclosure is a Type-4X weather-resistant, dust-tight, indoor/outdoor type. (Other 
enclosure options are described in Appendix C.) Typically, the electronics console is mounted in a meter shed. If it is 
not, select a location that allows you access to your meter for programming, testing, and servicing.
Note:  For compliance with the European Union’s Low Voltage  Directive, this unit requires an external power 
disconnect device such as a switch or circuit breaker. The disconnect device must be marked as such, clearly 
visible, directly accessible, and located within 6 ft (1.8 m) of the GF868.
1.3.2 Flowcell Location 
The pipeline flowcell consists of the flowmeter transducers and any pressure and temperature transducers that may be 
used as part of the flowmeter system. Ideally, the section of pipe chosen as the flowcell should be a pipe section with 
easy access; for example, a long stretch of pipe that is above ground. However, if the flowcell must be on an 
underground pipe, dig a pit around the pipe to facilitate the transducer mechanisms. 
1.3.3 Transducer Locations 
For a given gas and pipe, the Model GF868’s accuracy depends primarily on the location and alignment of the 
transducers on the pipe. In addition to accessibility, when planning for transducer location, consider the following 
guidelines: 
• Locate the transducers so that there are at least 20 pipe diameters of straight, undisturbed flow upstream and 10 
pipe diameters of straight, undisturbed flow downstream from the measurement point. To ensure undisturbed flow, 
avoid: sources of turbulence in the fluid such as valves, flanges, expansions and elbows; swirl; and dips or low 
spots in which condensed liquid may collect. 
• Because condensate or sediment that collects at the bottom of the pipe may cause increased attenuation of the 
ultrasonic signal, locate the transducers on the side of a horizontal pipe, where possible. If limited pipe access 
necessitates top-mounted transducers and the sound beam path includes a reflection, shift the transducers to at least 
10° off top center. This will minimize the influence of any sediment on the reflected ultrasonic signals. 
1.3.4 Cable Lengths
Locate the transducers as close as possible to the electronics console. The factory can supply transducer cables up to 
500 ft (153 m) in length. For longer distances, consult the factory.