5-136 G30 Generator Protection System GE Multilin
5.5 FLEXLOGIC 5 SETTINGS
5
INPUTS/OUTPUTS:
Remote double-
point status inputs
RemDPS Ip 1 BAD
RemDPS Ip 1 INTERM
RemDPS Ip 1 OFF
RemDPS Ip 1 ON
Asserted while the remote double-point status input is in the bad state
Asserted while the remote double-point status input is in the intermediate
state
Asserted while the remote double-point status input is off
Asserted while the remote double-point status input is on
REMDPS Ip 2 to 5 Same set of operands as per REMDPS 1
INPUTS/OUTPUTS:
Remote inputs
REMOTE INPUT 1 On
REMOTE INPUT 2 On
REMOTE INPUT 3 On
REMOTE INPUT 32 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
INPUTS/OUTPUTS:
Virtual inputs
Virt Ip 1 On
Virt Ip 2 On
Virt Ip 3 On
Virt Ip 64 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
INPUTS/OUTPUTS:
Virtual outputs
Virt Op 1 On
Virt Op 2 On
Virt Op 3 On
Virt Op 96 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
LED INDICATORS:
Fixed front panel
LEDs
LED IN SERVICE
LED TROUBLE
LED TEST MODE
LED TRIP
LED ALARM
LED PICKUP
LED VOLTAGE
LED CURRENT
LED FREQUENCY
LED OTHER
LED PHASE A
LED PHASE B
LED PHASE C
LED NEUTRAL/GROUND
Asserted when the front panel IN SERVICE LED is on
Asserted when the front panel TROUBLE LED is on
Asserted when the front panel TEST MODE LED is on
Asserted when the front panel TRIP LED is on
Asserted when the front panel ALARM LED is on
Asserted when the front panel PICKUP LED is on
Asserted when the front panel VOLTAGE LED is on
Asserted when the front panel CURRENT LED is on
Asserted when the front panel FREQUENCY LED is on
Asserted when the front panel OTHER LED is on
Asserted when the front panel PHASE A LED is on
Asserted when the front panel PHASE B LED is on
Asserted when the front panel PHASE C LED is on
Asserted when the front panel NEUTRAL/GROUND LED is on
LED INDICATORS:
LED test
LED TEST IN PROGRESS An LED test has been initiated and has not finished
LED INDICATORS:
User-programmable
LEDs
LED USER 1 Asserted when user-programmable LED 1 is on
LED USER 2 to 48 The operand above is available for user-programmable LEDs 2 through 48
PASSWORD
SECURITY
ACCESS LOC SETG OFF
ACCESS LOC SETG ON
ACCESS LOC CMND OFF
ACCESS LOC CMND ON
ACCESS REM SETG OFF
ACCESS REM SETG ON
ACCESS REM CMND OFF
ACCESS REM CMND ON
UNAUTHORIZED ACCESS
Asserted when local setting access is disabled
Asserted when local setting access is enabled
Asserted when local command access is disabled
Asserted when local command access is enabled
Asserted when remote setting access is disabled
Asserted when remote setting access is enabled
Asserted when remote command access is disabled
Asserted when remote command access is enabled
Asserted when a password entry fails while accessing a password protected
level of the G30
REMOTE DEVICES REMOTE DEVICE 1 On
REMOTE DEVICE 2 On
REMOTE DEVICE 3 On
REMOTE DEVICE 16 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
REMOTE DEVICE 1 Off
REMOTE DEVICE 2 Off
REMOTE DEVICE 3 Off
REMOTE DEVICE 16 Off
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
RESETTING RESET OP
RESET OP (COMMS)
RESET OP (OPERAND)
RESET OP (PUSHBUTTON)
Reset command is operated (set by all three operands below)
Communications source of the reset command
Operand (assigned in the
INPUTS/OUTPUTS  RESETTING menu) source
of the reset command
Reset key (pushbutton) source of the reset command
Table 5–17: G30 FLEXLOGIC OPERANDS (Sheet 7 of 8)
OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION