5-192 G30 Generator Protection System GE Multilin
5.6 GROUPED ELEMENTS 5 SETTINGS
5
Figure 5–79: SPLIT PHASE PROTECTION LOGIC
5.6.10 VOLTAGE ELEMENTS
a) MAIN MENU
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6)  VOLTAGE ELEMENTS
VOLTAGE ELEMENTS
PHASE
UNDERVOLTAGE1
See page 5–195.
MESSAGE
PHASE
UNDERVOLTAGE2
See page 5–195.
MESSAGE
PHASE
UNDERVOLTAGE3
See page 5–195.
830007A1.CDR
SPLIT PHASE BLOCK
SETTING
SPLIT PHASE SOURCE:
I_A
I_B
I_C
FLEXLOGIC OPERANDS
SPLIT PHASE PKP A
SPLIT PHASE OP A
AND
Off = 0
SETTING
SPLIT PHASE LOAD SOURCE:
I_1
START
SPLIT PHASE B PICKUP
SPLIT PHASE B OFFSET
SPLIT PHASE B SLOPE
SPLIT PHASE MIN LOAD
SPLIT PHASE MODE
SETTINGS
START
SPLIT PHASE C PICKUP
SPLIT PHASE C OFFSET
SPLIT PHASE C SLOPE
SPLIT PHASE MIN LOAD
SPLIT PHASE MODE
SETTINGS
t
0
SETTING
SPLIT PHASE DELAY
START
SPLIT PHASE A PICKUP
SPLIT PHASE A OFFSET
SPLIT PHASE A SLOPE
SPLIT PHASE MIN LOAD
SPLIT PHASE MODE
SETTINGS
t
0
SETTING
SPLIT PHASE DELAY
t
0
SETTING
SPLIT PHASE DELAY
OR
SPLIT PHASE DPO A
FLEXLOGIC OPERANDS
SPLIT PHASE PKP B
SPLIT PHASE OP B
SPLIT PHASE DPO B
FLEXLOGIC OPERANDS
SPLIT PHASE PKP C
SPLIT PHASE OP C
SPLIT PHASE DPO C
FLEXLOGIC OPERANDS
SPLIT PHASE OP
ACTUAL VALUES
SPLIT PHASE A CURRENT (PU)
SPLIT PHASE C CURRENT (PU)
SPLIT PHASE B CURRENT (PU)
LOAD CURRENT (PU)
SETTINGS
SPLIT PHASE FUNCTION
Enabled =1