EasyManua.ls Logo

GE G30 - Parallel Redundancy Protocol (Prp)

GE G30
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-12 G30 Generator Protection System GE Multilin
6.2 STATUS 6 ACTUAL VALUES
6
6.2.20 PARALLEL REDUNDANCY PROTOCOL (PRP)
The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation net-
works.
PATH: ACTUAL VALUES STATUS  PRP
The G30 Generator Protection System is provided with optional PRP capability. This feature is specified
as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
TOTAL RECEIVED PORT A is a counter for total messages received (either from DANPs or from SANs) on Port A.
TOTAL RECEIVED PORT B is a counter for total messages received (either from DANPs or from SANs) on Port B.
TOTAL ERRORS is a counter for total messages received with an error (bad port code, frame length too short).
MISMATCHES PORT A is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
MISMATCHES PORT B is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).
PRP
Total Rx Port A:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Total Rx Port B:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Total Errors:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Mismatches Port A:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Mismatches Port B:
Range: 0 to 4G, blank if PRP disabled

Table of Contents