iBox/iBox Kit
Installation and Maintenance Guide
GE Grid Solutions
150
994-0047-5.10-4 GE Information
iBox Kit with AC Analogs (IBOX-ACA)
Configuration Details Comments
DNP DPA
iBox DNP 3.0 Master Address: 10
iBox DNP 3.0 Slave Address: 1
Baud Rate: 9600
Communication Port: COM1
Communication Type: RS-232
Refer to point map tables for more detail.
Modbus DPA
Modbus Address: 1
Communication Port: COM2
Baud Rate: 9600
Communication Type: RS-232
Refer to point map tables for more detail.
WESMAINT
User Name: westronic
Password: rd
Control Password: control
Note: COM3 is used to connect the AC analog input module to the iBox.
IBOX Kit with DC Analogs (IBOX-DCA)
Configuration Details Comments
DNP DPA
iBox DNP 3.0 Master Address: 10
iBox DNP 3.0 Slave Address: 1
Baud Rate: 9600
Communication Port: COM1
Communication Type: RS-232
Refer to point map tables for more detail.
Modbus DPA
Modbus Address: 1
Communication Port: COM2
Baud Rate: 9600
Communication Type: RS-232
Refer to point map tables for more detail.
WESMAINT
User Name: westronic
Password: rd
Control Password: control
Note: COM3 is used to connect the DC analog input module to the iBox