Appendix C: Resetting the Digi One
Configuration
You can restore your Digi One configuration to the factory default configuration, as follows:
Procedure:
Resetting the
Digi One
Configuration
Step Action
1 Turn off power to the Digi One.
2 With a pointed object, such as small screwdriver or the point of a
paperclip, press and hold the recessed RESET switch, located on the
same side of the Digi One as the Ethernet connector:
3 While holding down the RESET button, restore power to the Digi One.
Result: The Digi One DIAG LED displays a 1–5–1 pattern after about
20 seconds.
4 When the 1–5–1 LED pattern is complete, release the RESET button.
Result: The Digi One boots up and its configuration resets to default.
The user name resets to root and the password to dbps.
5 Reconfigure the unit by following the procedure outlined in
“Configuring the Ethernet Module” on page 109.