GE Grid Solutions
iBox/iBox Kit
Installation and Maintenance Guide
GE Information
994-0047-5.10-4
Downloading Code Files, continued
Download Procedure, continued
Note
If the iBox does not have a code file loaded, or if it has detected a corrupt flash file,
you will have to go directly to Step 8 and log directly into the monitor.
Step Action
Launch System Monitor
3
Log into WESMAINT.
4
Select option 2, System Functions.
5
Select option 3, 68K Monitor.
Result: The D25A> prompt appears, indicating that the Application
Monitor is running.
6
At the D25A> prompt type rtb
ENTER.
For other available commands type help
ENTER.
7
At the Return to the BootROM Operating System? (yes/no) prompt,
type yes and press
ENTER
Note: The monitor is not case-sensitive, but Y is not acceptable
Result: The system restarts.
While the iBox is rebooting, the system is disabled.
Log in to the System Monitor
8
After the restart is complete, press
ENTER.
Result: The Login: prompt appears.
9
Type the login name westronic
ENTER and password rd ENTER.
Result: The system performs self-diagnostics to ascertain whether any
Flash EPROM memory is in use. The D25S> prompt appears,
indicating the System Monitor is running.
Clear Flash EPROM
10
Type erase
and press ENTER (not case-sensitive).
Result: The recommended procedure is to clear flash EPROM
memory, no matter what the system check reveals.
Continued on next page