MA-041 DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1 4-Mar-22 Page 70 of 99
Table 9-7: Results
Date:
____________
Primary B
(A1)
Ser No:
Primary B
(B1)
Ser No:
Primary C
(C1)
Ser No:
Primary B
(D1)
Ser No:
Secondary A
(A2)
Ser No:
Secondary B
(B2)
Ser No:
Secondary C
(C2)
Ser No:
Secondary C
(D2)
Ser No:
Section
Description
9.8.2.3
Bushing Adaptor ID
9.8.2.3
Mag Mount Temperature
Sensor (MMTS) # (3 single
phase install)
9.8.2.4.5
Bushing Adaptor Internal
Pin Correctly Installed
(Yes / No)
9.8.2.3
Manufacturer Nameplate
Power Factor % [PF%]
9.8.2.3
Manufacturer Nameplate
Capacitance [C1]
9.8.2.3
Manufacturer Nameplate
Capacitance [C2]
9.8.2.3
Manufacturer Nameplate
[T]
9.8.2.4.1
Shield to ground resistance
Test (<5 Ohm)
9.8.2.4.2
Coaxial cable core and
shield resistance Test [R1]
(<3000 )
9.8.2.4.3
Input resistance Test [R2]
(<2000 )
9.8.2.4.4
Total resistance Test [R3]
9.8.2.4.4
[R3] within 5% of the
[R
input
] (Yes or No)
9.8.2.4.5
(when the transformer is
energised)
Input voltage Test
Expected 0.9 1.4 v RMS