CR194 Two-High Vacuum Limitamp@ Control
LINE SibE CONNECTIONS
CI,
Figure 20. View showing stationary contactor line side cable
connections at the power fuses
Step 7.
Slide the contactor forward approximately four (4)
inches until the slide safety stop engages in the plate
that is attached to the bottom of the contactor. The
safety stop is located on the left side of the contactor
mounting track. Figure 21 shows the safety stop for
a stationary contactor with the contactor removed
for clarity.
from the enclosure, be aware that the contactor
weighs 75 pounds and should be handled very care-
fully & deliberately using both hands. Do not grasp
the contactor by the top moving armature.
NOTE:
A platform lift jack is available from GE that can be
used to aid in contactor removal and transport. Order cata-
log No. 55B534913PI.
Step 8.
To
completely remove the contactor from the
enclosure, pull up on the safety stop and move the
contactor forward about one (1) inch. Then release
the safety stop and grasp the contactor with both
hands and move it forward and out of the enclosure.
Do not grasp the contactor by the top
moving armature.
Figure 21. View of slide safety stop and
main bus barriers with stationary contactor removed
13