CR194 Two-High Vacuum Limitamp@’ Control 
Step  5. 
While  pulling  on  the  high-voltage  door,  lift  up  on  the 
defeater  bracket  as shown  in  Figure  48  to  allow  the 
high-voltage  door  to  open. 
Figure  48.  Lift  defeater  bracket  while  pulling 
high-voltage 
door 
Step  6. 
To  close  the  high-voltage  door  with  the  isolation 
switch  handle  in  the  “on”  position,  the  procedure 
must  be  done  in  reverse  order,  making  sure  to  rein- 
stall  the  door  interlock  defeater  locking  bolt. 
INSPECTION, 
MAINTENANCE  &  SERVICING 
WARNING: 
Before  performing  any  inspection, 
maintenance  or  servicing  on  the  equipment  all 
all  load-connected  rotating  equipment  must  have 
Mechanical  Operation  Check 
Begin  any  inspection,  maintenance  and  servicing  rou- 
tine  by first  performing  all  the  checks  in  the  “Mechani- 
cal  Operation  Check”  section,  which  is part  of  the  “In- 
stallation”  section  of  this  instruction.  This  includes: 
Isolation  Switch  Handle  to  Contactor 
Mechanical  Interlock 
Handle  and  Isolation  Switch  Operation 
High-Voltage  Door  Safety  Interlock 
Control  Power  Interlock  (CPI) 
Test  Power  Interlock  (TPI) 
Vacuum  Interrupter  Integrity Test 
Then  perform  the  “Vacuum  Interrupter  Integrity 
Test”,  which  is a part  of  the  “Installation”  section  of 
this  instruction. 
Vacuum  Contactor 
Complete  maintenance  and  adjustment  instructions 
for  the  high-voltage  contactor  are  presented  in  GEH- 
5306.  Refer  to  that  instruction  for  all  problems  of  ser- 
vicing  and  adjusting  the  contactor  and  to  the  proper 
renewal  parts  bulletin  for  renewal  parts  for  the 
contactor. 
Contactor  tip  life  depends  on  the  severity  of  the  ser- 
vice,  but  in  any  case,  it  is recommended  that  the 
contactor  tip  wear  be  checked  at  least  once  a year,  or 
in  very  high  duty  cycle  situations,  after  every  250,000 
operations. 
Isolation  Mechanism 
WARNING: 
Under  no  circumstances  should  the 
isolation  switch  be  inspected  or  adjusted  with 
power  applied  to  the  main  bus. 
The  quick-make,  quick-break  isolation  switch  assembly 
is adjusted  and  tested  at  the  factory  and  under  normal 
circumstances  does  not  need  adjustment.  However,  if 
conditions  require,  the  switch  can  be  adjusted  in  the 
field  by following  the  steps  below. 
28