Installation Guide LP33 Series 20 & 30 UL S2
4.5 VENTILATION AND COOLING
The heat produced by the UPS is transferred to the environment by its internal fan(s).
Fig. 4.5-1 Airflow through the LP33 Series 20 & 30
Airflow through the UPS
It is important that the cooling air can freely flow
through the air inlets and outlets of the UPS.
NOTE !
Insufficient distances on both sides of the
UPS could increase the temperature inside
the UPS.
Do not put any object on the top of the
cabinet: it might obstruct the air flow.
Heat evacuation from UPS
room
The heat must be evacuated
from the environment with a
proper cooling / ventilation
system provided by the user.
Fig. 4.5-2 Heat evacuation from UPS room
Air volume and losses of the UPS
The approximate minimum air volume needed to evacuate the heat generated by the UPS, for inlet
temperature max. 35°C (95°F), for the standard version at inverter nominal load with PF = 0.8 lag. and
battery charged, are the following:
NOTE !
Even when ECO Mode option is available, the ventilation and cooling system shall be
rated as for operation in VFI mode.