GE MiCOM P141 Agile - Figure 103: Circuit Breaker Fail Logic - Single Phase Start

GE MiCOM P141 Agile
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V00657
External Trip A
IA< Start
Ext Prot Reset
I< Only
CB Open & I<
Prot Reset & I<
Pole Dead A
External Trip A
ZCD IA<
CBFExtPhAStart
CBFExtPhBStart
CBFExtPhCStart
CB Fail Alarm
1
&
S
RD
Q
S
R
D
Q
1
1
&
&
External Trip B
IB< Start
Ext Prot Reset
I< Only
CB Open & I<
Prot Reset & I<
Pole Dead B
External Trip B
ZCD IB<
CB Fail Alarm
1
&
S
R
D
Q
S
RD
Q
1
1
&
&
External Trip C
IC< Start
Ext Prot Reset
I< Only
CB Open & I<
Prot Reset & I<
Pole Dead C
External Trip C
ZCD IC<
CB Fail Alarm
1
&
S
RD
Q
S
R
D
Q
1
1
&
&
Note on SR Latches
All latches are reset dominant and are triggered on the positive edge . If
the edge occurs while the reset is active , the detection of the edge is
delayed until the reset becomes non -active.
Figure 103: Circuit Breaker Fail logic - single phase start
Chapter 8 - CB Fail Protection P14x
188 P14xEd1-TM-EN-1