CHAPTER 1: INTRODUCTION SPECIFICATIONS
MM200 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 1–11
EAC
The EAC Technical Regulations (TR) for Machines and Equipment apply to the Customs
Union (CU) of the Russian Federation, Belarus, and Kazakhstan
Power Frequency Immunity EN61000-4-7/IEC60255-22-7 Class A
Voltage interruptionand Ripple DC IEC60255-11 15% ripple, 200ms interupts
Radiated & Conducted Emissions CISPR11 /CISPR22/ IEC60255-25 Class A
Sinusoidal Vibration IEC60255-21-1 Class 1
Shock & Bump IEC60255-21-2 Class 1
Siesmic IEC60255-21-3 Class 2
Power magnetic Immunity IEC61000-4-8 Level 5
Pulse Magnetic Immunity IEC61000-4-9 Level 4
Damped Magnetic Immunity IEC61000-4-10 Level 4
Voltage Dip & interruption IEC61000-4-11 0,40,70% dips,250/300cycle
interrupts
Damped Oscillatory IEC61000-4-12 2.5KV CM, 1KV DM
Voltage Ripple IEC61000-4-17 15% ripple
Ingress Protection IEC60529 IP20 (base unit) , IP54
(Control Panel)
Environmental (Cold) IEC60068-2-1 -25C 16 hrs
Environmental (Dry heat) IEC60068-2-2 70C 16hrs
Relative Humidity Cyclic IEC60068-2-30 6day variant 2
UL508 e83849 NKCR
Safety UL C22.2-14 e83849 NKCR7
UL1053 e83849 NKCR
CERTIFICATION
APPROVAL
Applicable Council Directive According to
Low voltage directive EN60255-5, EN60255-27
CE compliance EMC Directive EN60255-26 / EN50263
UL508
North America cULus UL1053
C22.2.No 14
EAC Machines and Equipment TR CU 010/2011
ISO: Manufactured under a registered
quality program
ISO9001
Item Description
Country of origin Spain or Canada; see label on the unit
Date of manufacture See label on the side of the MM200 unit
Declaration of Conformity and/or Certificate of
Conformity
Available on request
TYPE TESTS
Test Reference Standard Test Level