4–10 MM200 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CONFIGURATION SETPOINTS CHAPTER 4: SETPOINTS
DeviceNet MAC ID
Range: 0 to 63 in steps of 1
Default: 63
This setpoint specifies the dedicated MAC ID as per the DeviceNet design.
DeviceNet Baud Rate
Range: 125, 250, or 500 kbps
Default: 125 kbps
This setpoint selects the DeviceNet baud rate.
Profibus Address
Range: 1 to 125
Default: 1
This setpoint allows the user to select the appropriate Profibus address.
Profibus Baud Rate
Range: 9600 to 1.5 M
Default: 1.5 M
This setpoint selects the Profibus baud rate.
Comms OK Evaluation
Range: Serial, Serial + Fieldbus, Fieldbus, All
Default: Serial
Specifies the operands for the Comms OK flag.
Comm Failure Trip
Range: Off, 1 to 29 step 1s
Default: Off
Specifies the time without comms before a trip will be generated.
Comm Failure Alarm
Range: Off, 1 to 29 step 1s
Default: Off
Specifies the time without comms before an alarm will be generated.
NOTE
NOTE:
Timing delay commences after failure is detected.
Change Mode on Comm Alarm
Range: Disabled, Enabled
Default: Disabled
If enabled, forces control mode to manual if comms are lost.