CHAPTER 4: SETPOINTS CONTROL ELEMENTS
MM200 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 4–25
Comms Start Ctrl
Range: Enabled, Disabled
Default: Disabled
Sets whether start commands are accepted via communications.
Comms Stop Mode
Range: Always Enabled, Follow Ctrl Mode
Default: Always Enabled
If set to “Always Enabled”, communication stops will always be honoured, irrespective of
the
Comms Start Ctrl setpoint and auto/manual mode. If set to “Follow Ctrl Mode”,
communication stops will be supervised by auto/manual and by communication
permissive in the same manner as the starts.
Hard Wired Start Ctrl
Range: Enabled, Disabled
Default: Disabled
Sets whether start commands are accepted from hard wired start contact inputs.
Hard Wired Stop Mode
Range: Always Enabled, Follow Ctrl Mode
Default: Always Enabled
If set to “Always Enabled”, hard-wired stops will always be honoured, irrespective of the
Hard Wired Start Ctrl setpoint, auto/manual mode and permissive. If set to “Follow Ctrl
Mode”, hard-wired stops will be supervised by auto/manual and by hard-wired
permissive in the same manner as the starts.
Hard Wired Stop Actn
Range: Stop, Trip
Default: Stop
Defines whether hard wired stop control trips (reset required to clear) or stops (no reset
required).
Hard Wired 2W/3W
Range: 2W, 3W
Default: 3W
The setpoint is for two-wire or three-wire control selection. If in the two-wire mode, all
hard-wired start contact inputs being open will be treated as a hard-wired stop control.
For reversing and two-speed starter configurations, both start inputs open is treated as
a hard-wired stop control.
Field Start Ctrl
Range: Enabled, Disabled
Default: Disabled
Sets whether start commands are accepted from field start contact inputs.
Field Stop Mode
Range: Always Enabled, Follow Ctrl Mode
Default: Always Enabled
If set to “Always Enabled”, field stops will always be honoured, irrespective of the
Field
Start Ctrl setpoint, auto/manual mode, and permissive. If set to “Follow Ctrl Mode”, field
stops will be supervised by auto/manual and by field permissive in the same manner as
the starts.
Field Stop Action
Range: Stop, Trip
Default: Stop
Defines whether field control trips (reset required to clear) or stops (no reset required).