42
Sub Meters GE Multilin
5.7.3. Three Phase 4 Wire Star (Wye)
3 CTs. Direct Voltage Connections if Voltages are less than 600v AC L-L. Otherwise, 3 PTs.
For Single Phase, the same diagram is used except that only Phase 1 connections exist and
Phase 2 and Phase 3 are unused. The unused current terminals must be shorted together to
reduce noise picked up in the meter.