6.5.6. Forward Integrator Block
Start Address: 3120
Block Size: 20 Registers
Modbus Read Function Code: 03
Always transfer the Whole Block.
Add
res
s
Parameters Description Data Type
3120
VAh (Fwd) Forward Apparent Energy 32-bit Float
3122
Wh (Fwd) Forward Active Energy 32-bit Float
3124
VARh_L (Fwd) Forward Reactive Inductive Energy 32-bit Float
3126
RESERVED5 Reserved for future use 32-bits
3128
RESERVED6 Reserved for future use 32-bits
3130
VARh_C (Fwd)
Forward Reactive Capacitive
Energy
32-bit Float
3132
RESERVED7 Reserved for future use 32-bits
3134
RESERVED8 Reserved for future use 32-bits
3136
RESERVED9 Reserved for future use 32-bits
3138
RUN_SECS
(Fwd)
Forward Seconds Meter Load was
connected since last Reset
32-bit Unsigned Long