50
Sub Meters GE Multilin
6.5.7.
6.5.8. Favorite Block
• Start Address: 3900
• Block Size: 100 Registers
•
Modbus Read Function Code: 03
•
Transfer the Whole Block or Individual Parameter
Addr
ess
Parameters Description Data Type
3900
VA Total RMS Apparent Power 32-bit Float
3902
W Total RMS Active Energy 32-bit Float
3904
VAR Total RMS Reactive Energy 32-bit Float
3906
PF Total RMS PF 32-bit Float
3908
VLL Total RMS Line to Line Voltage 32-bit Float
3910
VLN
Total RMS Line to Neutral
Voltage
32-bit Float
3912
A Total RMS Current 32-bit Float
3914
F Total RMS Frequency 32-bit Float
3916
VA
A
RMS Phase A Apparent Power 32-bit Float
3918
W
A
RMS Phase A Active Energy 32-bit Float
3920
VAR
A
RMS Phase A Reactive Energy 32-bit Float
3922
PF
A
RMS Phase A PF 32-bit Float
3924
V
AB
RMS Phase A Line to Line
Voltage
32-bit Float
3926
V
A
RMS Phase A Line to Neutral
Voltage
32-bit Float
3928
A
A
RMS Phase A Current 32-bit Float
3930
VA
B
RMS Phase B Apparent Power 32-bit Float
3932
W
B
RMS Phase B Active Energy 32-bit Float
3934
VAR
B
RMS Phase B Reactive Energy 32-bit Float
3936
PF
B
RMS Phase B PF 32-bit Float
3938
V
BC
RMS Phase B Line to Line
Voltage
32-bit Float
3940
V
B
RMS Phase B Line to Neutral
Voltage
32-bit Float
3942
A
B
RMS Phase B Current 32-bit Float
3944
VA
C
RMS Phase C Apparent Power 32-bit Float
3946
W
C
RMS Phase C Active Energy 32-bit Float
3948
VAR
C
RMS Phase C Reactive Energy 32-bit Float
3950
PF
C
RMS Phase C PF 32-bit Float
3952
V
CA
RMS Phase C Line to Line
Voltage
32-bit Float
3954
V
C
RMS Phase C Line to Neutral
Voltage
32-bit Float
3956
A
C
RMS Phase C Current 32-bit Float
3958
VAh (Fwd) Forward Apparent Energy 32-bit Float
3960
Wh (Fwd) Forward Active Energy 32-bit Float