GE Multilin N60 Network Stability and Synchrophasor Measurement System B-19
APPENDIX B B.4 MEMORY MAPPING
B
1D8A Frequency for Source 6 2 to 90 Hz 0.001 F003 0
Source Demand (Read Only) (6 Modules)
1E00 Source 1 Demand Ia 0 to 999999.999 A 0.001 F060 0
1E02 Source 1 Demand Ib 0 to 999999.999 A 0.001 F060 0
1E04 Source 1 Demand Ic 0 to 999999.999 A 0.001 F060 0
1E06 Source 1 Demand Watt 0 to 999999.999 W 0.001 F060 0
1E08 Source 1 Demand Var 0 to 999999.999 var 0.001 F060 0
1E0A Source 1 Demand Va 0 to 999999.999 VA 0.001 F060 0
1E0C Reserved (4 items) --- --- --- F001 0
1E10 ...Repeated for Source 2
1E20 ...Repeated for Source 3
1E30 ...Repeated for Source 4
1E40 ...Repeated for Source 5
1E50 ...Repeated for Source 6
Source Demand Peaks (Read Only Non-Volatile) (6 Modules)
1E80 Source 1 Demand Ia Maximum 0 to 999999.999 A 0.001 F060 0
1E82 Source 1 Demand Ia Maximum Date 0 to 4294967295 --- 1 F050 0
1E84 Source 1 Demand Ib Maximum 0 to 999999.999 A 0.001 F060 0
1E86 Source 1 Demand Ib Maximum Date 0 to 4294967295 --- 1 F050 0
1E88 Source 1 Demand Ic Maximum 0 to 999999.999 A 0.001 F060 0
1E8A Source 1 Demand Ic Maximum Date 0 to 4294967295 --- 1 F050 0
1E8C Source 1 Demand Watt Maximum 0 to 999999.999 W 0.001 F060 0
1E8E Source 1 Demand Watt Maximum Date 0 to 4294967295 --- 1 F050 0
1E90 Source 1 Demand Var 0 to 999999.999 var 0.001 F060 0
1E92 Source 1 Demand Var Maximum Date 0 to 4294967295 --- 1 F050 0
1E94 Source 1 Demand Va Maximum 0 to 999999.999 VA 0.001 F060 0
1E96 Source 1 Demand Va Maximum Date 0 to 4294967295 --- 1 F050 0
1E98 Reserved (8 items) --- --- --- F001 0
1EA0 ...Repeated for Source 2
1EC0 ...Repeated for Source 3
1EE0 ...Repeated for Source 4
1F00 ...Repeated for Source 5
1F20 ...Repeated for Source 6
Passwords Unauthorized Access (Read/Write Command)
2230 Reset Unauthorized Access 0 to 1 --- 1 F126 0 (No)
Synchrocheck Actuals (Read Only) (4 Modules)
2400 Synchrocheck 1 Delta Voltage -1000000000000 to
1000000000000
V1F060 0
2402 Synchrocheck 1 Delta Frequency 0 to 655.35 Hz 0.01 F001 0
2403 Synchrocheck 1 Delta Phase 0 to 359.9 degrees 0.1 F001 0
2404 ...Repeated for Synchrocheck 2
2408 ...Repeated for Synchrocheck 3
240C ...Repeated for Synchrocheck 4
Field Unit Raw Data Settings (Read/Write Setting)
2460 Field Raw Data Port 0 to 7 --- 1 F244 6 (H1a)
2461 Field Raw Data Freeze 0 to 1 --- 1 F102 0 (Disabled)
Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 Modules)
2540 Remote Double-point Status Input 1 Device 1 to 32 --- 1 F001 1
2541 Remote Double-point Status Input 1 Item 0 to 64 --- 1 F606 0 (None)
2542 Remote Double-point Status Input 1 Name 1 to 64 --- 1 F205 "RemDPS Ip 1"
2548 Remote Double-point Status Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
2549 ... Repeated for double-point status input 2
2552 ... Repeated for double-point status input 3
255B ... Repeated for double-point status input 4
Table B–10: MODBUS MEMORY MAP (Sheet 11 of 70)