B-20 N60 Network Stability and Synchrophasor Measurement System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
2564 ... Repeated for double-point status input 5
Phasor Measurement Unit Actual Values (Read Only) (6 Modules)
256D PMU 1 Phase A Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
256F PMU Unit 1 Phase A Voltage Angle -180 to 180 ° 0.1 F002 0
2570 PMU 1 Phase B Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2572 PMU 1 Phase B Voltage Angle -180 to 180 ° 0.1 F002 0
2573 PMU 1 Phase C Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2575 PMU 1 Phase C Voltage Angle -180 to 180 ° 0.1 F002 0
2576 PMU 1 Auxiliary Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2578 PMU 1 Auxiliary Voltage Angle -180 to 180 ° 0.1 F002 0
2579 PMU 1 Positive Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
257B PMU 1 Positive Sequence Voltage Angle -180 to 180 ° 0.1 F002 0
257C PMU 1 Negative Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
257E PMU 1 Negative Sequence Voltage Angle -180 to 180 ° 0.1 F002 0
257F PMU 1 Zero Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2581 PMU 1 Zero Sequence Voltage Angle -180 to 180 ° 0.1 F002 0
2582 PMU 1 Phase A Current Magnitude 0 to 999999.999 A 0.001 F060 0
2584 PMU 1 Phase A Current Angle -180 to 180 ° 0.1 F002 0
2585 PMU 1 Phase B Current Magnitude 0 to 999999.999 A 0.001 F060 0
2587 PMU 1 Phase B Current Angle -180 to 180 ° 0.1 F002 0
2588 PMU 1 Phase C Current Magnitude 0 to 999999.999 A 0.001 F060 0
258A PMU 1 Phase C Current Angle -180 to 180 ° 0.1 F002 0
258B PMU 1 Ground Current Magnitude 0 to 999999.999 A 0.001 F060 0
258D PMU 1 Ground Current Angle -180 to 180 ° 0.1 F002 0
258E PMU 1 Positive Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2590 PMU 1 Positive Sequence Current Angle -180 to 180 ° 0.1 F002 0
2591 PMU 1 Negative Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2593 PMU 1 Negative Sequence Current Angle -180 to 180 ° 0.1 F002 0
2594 PMU 1 Zero Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2596 PMU 1 Zero Sequence Current Angle -180 to 180 ° 0.1 F002 0
2597 PMU 1 Frequency 2 to 90 Hz 0.001 F003 0
2599 PMU 1 df/dt -327.67 to 327.67 Hz/s 0.01 F002 0
259A PMU 1 Configuration Change Counter 0 to 655.35 0.01 F001 0
259B Reserved (4 items) 0 to 1 --- 1 F001 0
259F ...Repeated for PMU 2
25D1 ...Repeated for PMU 3
2603 ...Repeated for PMU 4
2635 ...Repeated for PMU 5
2667 ...Repeated for PMU 6
Phasor Measurement Unit Integer Values (Read Only Actual Value Registers) (1, 2, 4, or 6 Modules)
2699 PMU 1 SOC Timestamp 0 to 4294967295 seconds 1 F003 0
269B PMU 1 FRAMESEC Timestamp 0 to 4294967295 seconds 1 F003 0
269D PMU 1 STAT Flags 0 to 4294967295 --- 1 F003 0
269F ...Repeated for PMU 2
26A5 ...Repeated for PMU 3
26AB ...Repeated for PMU 4
26B1 ...Repeated for PMU 5
26B7 ...Repeated for PMU 6
Phasor Measurement Unit Aggregator Actual Values (Read Only) (1, 2, or 4 Modules)
26BD PMU 1 Aggregator PDU Size --- --- --- F001 0
26BE ...Repeated for PMU 2
26BF ...Repeated for PMU 3
26C0 ...Repeated for PMU 4
Table B–10: MODBUS MEMORY MAP (Sheet 12 of 70)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT