B-46 N60 Network Stability and Synchrophasor Measurement System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
8364 ...Repeated for Switch 5
838D ...Repeated for Switch 6
Direct Integers (Read/Write Setting) (16 Modules)
8540 Direct Integer Output 1 Value 0 to 65535 --- 1 F612 0
8541 Direct Integer Output 1 Trigger 0 to 4294967295 --- 1 F300 0
8543 Direct Integer Input 1 Device 0 to 16 --- 1 F001 0
8544 Direct Integer Input 1 Number 0 to 16 --- 1 F001 0
8545 Direct Integer Input 1 Default Value 0 to 4294967295 --- 1 F003 1000
8547 Direct Integer Input 1 Mode 0 to 1 --- 1 F491 0 (Default Value)
8548 Direct Integer Reserved 0 to 65535 --- 1 F003 0
854A ...Repeated for Direct Integer Output 2
8554 ...Repeated for Direct Integer Output 3
855E ...Repeated for Direct Integer Output 4
8568 ...Repeated for Direct Integer Output 5
8572 ...Repeated for Direct Integer Output 6
857C ...Repeated for Direct Integer Output 7
8586 ...Repeated for Direct Integer Output 8
8590 ...Repeated for Direct Integer Output 9
859A ...Repeated for Direct Integer Output 10
85A4 ...Repeated for Direct Integer Output 11
85AE ...Repeated for Direct Integer Output 12
85B8 ...Repeated for Direct Integer Output 13
85C2 ...Repeated for Direct Integer Output 14
85CC ...Repeated for Direct Integer Output 15
85D6 ...Repeated for Direct Integer Output 16
FlexState Settings (Read/Write Setting)
8800 FlexState Parameters (256 items) 0 to 4294967295 --- --- F300 0
Digital Elements (Read/Write Setting) (48 Modules)
8A00 Digital Element 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8A01 Digital Element 1 Name --- --- --- F203 “Dig Element 1“
8A09 Digital Element 1 Input 0 to 4294967295 --- 1 F300 0
8A0B Digital Element 1 Pickup Delay 0 to 999999.999 s 0.001 F003 0
8A0D Digital Element 1 Reset Delay 0 to 999999.999 s 0.001 F003 0
8A0F Digital Element 1 Block 0 to 4294967295 --- 1 F300 0
8A11 Digital Element 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
8A12 Digital Element 1 Events 0 to 1 --- 1 F102 0 (Disabled)
8A13 Digital Element 1 Pickup LED 0 to 1 --- 1 F102 1 (Enabled)
8A14 Reserved (2 items) --- --- --- F001 0
8A16 ...Repeated for Digital Element 2
8A2C ...Repeated for Digital Element 3
8A42 ...Repeated for Digital Element 4
8A58 ...Repeated for Digital Element 5
8A6E ...Repeated for Digital Element 6
8A84 ...Repeated for Digital Element 7
8A9A ...Repeated for Digital Element 8
8AB0 ...Repeated for Digital Element 9
8AC6 ...Repeated for Digital Element 10
8ADC ...Repeated for Digital Element 11
8AF2 ...Repeated for Digital Element 12
8B08 ...Repeated for Digital Element 13
8B1E ...Repeated for Digital Element 14
8B34 ...Repeated for Digital Element 15
8B4A ...Repeated for Digital Element 16
8B60 ...Repeated for Digital Element 17
Table B–10: MODBUS MEMORY MAP (Sheet 38 of 70)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT