B-76 N60 Network Stability and Synchrophasor Measurement System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
EA46 ...Repeated for PMU 6
Phasor Measurement Unit Triggering (Read/Write Setting) (1, 2, 4, or 6 Modules)
EA4A PMU 1 User Trigger 0 to 4294967295 --- 1 F300 0
EA4C ...Repeated for PMU 2
EA4E ...Repeated for PMU 3
EA50 ...Repeated for PMU 4
EA52 ...Repeated for PMU 5
EA54 ...Repeated for PMU 6
Phasor Measurement Unit Voltage Trigger (Read/Write Setting) (1, 2, 4, or 6 Modules)
EA56 PMU 1 Volt Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EA57 PMU 1 Voltage Trigger Low Volt 0.25 to 1.25 pu 0.001 F001 800
EA58 PMU 1 Voltage Trigger High Volt 0.75 to 1.75 pu 0.001 F001 1200
EA59 PMU 1 Voltage Trigger Pkp Time 0 to 600 s 0.01 F001 10
EA5A PMU 1 Voltage Trigger Dpo Time 0 to 600 s 0.01 F001 100
EA5B PMU 1 Voltage Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
EA61 PMU 1 Voltage Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EA62 PMU 1 Voltage Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
EA63 ...Repeated for PMU 2
EA70 ...Repeated for PMU 3
EA7D ...Repeated for PMU 4
EA8A ...Repeated for PMU 5
EA97 ...Repeated for PMU 6
Phasor Measurement Unit Current Trigger (Read/Write Setting (1, 2, 4, or 6 Modules)
EAA4 PMU 1 Current Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EAA5 PMU 1 Current Trigger Pickup 0.1 to 30 pu 0.001 F001 1800
EAA6 PMU 1 Current Trigger Pkp Time 0 to 600 s 0.01 F001 10
EAA7 PMU 1 Current Trigger Dpo Time 0 to 600 s 0.01 F001 100
EAA8 PMU 1 Current Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
EAAE PMU 1 Current Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EAAF PMU 1 Current Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
EAB0 ...Repeated for PMU 2
EABC ...Repeated for PMU 3
EAC8 ...Repeated for PMU 4
EAD4 ...Repeated for PMU 5
EAE0 ...Repeated for PMU 6
Phasor Measurement Unit Frequency Trigger (Read/Write Setting) (1, 2, 4, or 6 Modules)
EAEC PMU 1 Frequency Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EAED PMU 1 Frequency Trigger Low Frequency 20 to 70 Hz 0.01 F001 4900
EAEE PMU 1 Frequency Trigger High Frequency 20 to 70 Hz 0.01 F001 6100
EAEF PMU 1 Frequency Trigger Pickup Time 0 to 600 s 0.01 F001 10
EAF0 PMU 1 Frequency Trigger Dropout Time 0 to 600 s 0.01 F001 100
EAF1 PMU 1 Frequency Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
EAF7 PMU 1 Frequency Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EAF8 PMU 1 Frequency Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
EAF9 ...Repeated for PMU 2
EB06 ...Repeated for PMU 3
EB13 ...Repeated for PMU 4
EB20 ...Repeated for PMU 5
EB2D ...Repeated for PMU 6
Phasor Measurement Unit df/dt Trigger (Read/Write Setting) (1, 2, 4, or 6 Modules)
EB3A PMU 1 df/dt Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EB3B PMU 1 df/dt Trigger Raise 0.1 to 15 Hz/s 0.01 F001 25
EB3C PMU 1 df/dt Trigger Fall 0.1 to 15 Hz/s 0.01 F001 25
EB3D PMU 1 df/dt Trigger Pkp Time 0 to 600 s 0.01 F001 10
Table B–10: MODBUS MEMORY MAP (Sheet 68 of 70)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT