GE Multilin N60 Network Stability and Synchrophasor Measurement System B-77
APPENDIX B B.4 MEMORY MAPPING
B
EB3E PMU 1 df/dt Trigger Dpo Time 0 to 600 s 0.01 F001 100
EB3F PMU 1 df/dt Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
EB45 PMU 1 df/dt Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EB46 PMU 1 df/dt Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
EB47 ...Repeated for PMU 2
EB54 ...Repeated for PMU 3
EB61 ...Repeated for PMU 4
EB6E ...Repeated for PMU 5
EB7B ...Repeated for PMU 6
Phasor Measurement Unit Power Trigger (Read/Write Setting) (1, 2, 4, or 6 Modules)
EB88 PMU 1 Power Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EB89 PMU 1 Power Trigger Active 0.25 to 3 pu 0.01 F001 1250
EB8A PMU 1 Power Trigger Reactive 0.25 to 3 pu 0.01 F001 1250
EB8B PMU 1 Power Trigger Apparent 0.25 to 3 pu 0.01 F001 1250
EB8C PMU 1 Power Trigger Pkp Time 0 to 600 s 0.01 F001 10
EB8D PMU 1 Power Trigger Dpo Time 0 to 600 s 0.01 F001 100
EB8E PMU 1 Power Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
EB94 PMU 1 Power Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EB95 PMU 1 Power Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
EB96 ...Repeated for PMU 2
EBA4 ...Repeated for PMU 3
EBB2 ...Repeated for PMU 4
EBC0 ...Repeated for PMU 5
EBCE ...Repeated for PMU 6
Phasor Measurement Unit Calibration (Read/Write Setting) (1, 2, 4, or 6 Modules)
EBDC PMU Va Calibration Angle -5 to 5 ° 0.05 F002 0
EBDD PMU Va Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBDE PMU Vb Calibration Angle -5 to 5 ° 0.05 F002 0
EBDF PMU Vb Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBE0 PMU Vc Calibration Angle -5 to 5 ° 0.05 F002 0
EBE1 PMU Vc Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBE2 PMU Vx Calibration Angle -5 to 5 ° 0.05 F002 0
EBE3 PMU Vx Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBE4 PMU Ia Calibration Angle -5 to 5 ° 0.05 F002 0
EBE5 PMU Ia Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBE6 PMU Ib Calibration Angle -5 to 5 ° 0.05 F002 0
EBE7 PMU Ib Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBE8 PMU Ic Calibration Angle -5 to 5 ° 0.05 F002 0
EBE9 PMU Ic Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBEA PMU Ig Calibration Angle -5 to 5 ° 0.05 F002 0
EBEB PMU Ig Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBEC PMU Sequence Voltage Shift Angle -180 to 180 ° 30 F002 0
EBED PMU Sequence Current Shift Angle -180 to 180 ° 30 F002 0
EBEE ...Repeated for PMU 2
EC00 ...Repeated for PMU 3
EC12 ...Repeated for PMU 4
EC24 ...Repeated for PMU 5
EC36 ...Repeated for PMU 6
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
EC48 PMU Network Reporting Function 0 to 1 --- 1 F102 0 (Disabled)
EC49 PMU Network Reporting ID Code 1 to 65534 --- 1 F001 1
EC4A PMU TCP port number 1 to 65535 --- 1 F001 4712
EC4B PMU UDP port number 1 1 to 65535 --- 1 F001 4713
EC4C PMU UDP port number 2 1 to 65535 --- 1 F001 4714
Table B–10: MODBUS MEMORY MAP (Sheet 69 of 70)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT