Appendix B - Settings and Signals
P54A/B/C/E
B236
P54xMED-TM-EN-1
ORDINAL SIGNAL NAME ELEMENT NAME
DESCRIPTION
possible for them to fail to resolve this in which case they produce the DDB_CONFIGURATION_ERROR alarm
336
Re-Config Error
DDB_RE_CONFIGURATION_ERROR
Indicates that RESTORE or RECONFIGURE or CONFIGURE operations have failed
338
Max Prop. Alarm
DDB_MAX_PROP_DELAY_ALARM
Maximum Propagation Delay Alarm
339
CDiff Inhibit
DDB_TEST_MODE_CDIFF_INHIBIT
Cdiff Inhibit from Test Mode
340
Prot'n Disabled
DDB_PROTECTION_DISABLED
Protection disabled - typically out of service due to test mode
344
SR User Alarm 1
DDB_ALARM_56
Triggers user alarm 1 message to be alarmed on LCD display (self-resetting)
345
SR User Alarm 2
DDB_ALARM_57
Triggers user alarm 2 message to be alarmed on LCD display (self-resetting)
346
SR User Alarm 3
DDB_ALARM_58
Triggers user alarm 3 message to be alarmed on LCD display (self-resetting)
347
SR User Alarm 4
DDB_ALARM_59
Triggers user alarm 4 message to be alarmed on LCD display (self-resetting)
348
MR User Alarm 5
DDB_ALARM_60
Triggers user alarm 5 message to be alarmed on LCD display (manual-resetting)
349
MR User Alarm 6
DDB_ALARM_61
Triggers user alarm 6 message to be alarmed on LCD display (manual-resetting)
350
MR User Alarm 7
DDB_ALARM_62
Triggers user alarm 7 message to be alarmed on LCD display (manual-resetting)
351
MR User Alarm 8
DDB_ALARM_63
Triggers user alarm 8 message to be alarmed on LCD display (manual-resetting)
352
Battery Fail
DDB_BATTERY_FAIL
Front panel miniature battery failure - either battery removed from slot, or low voltage
354
Rear Comm 2 Fail
DDB_REAR_COMMS_FAIL
Comm2 hardware failure - second rear communications board
355
GOOSE IED Absent
DDB_GOOSE_MISSING_IED
The IED is not subscribed to a publishing IED in the current scheme
356
NIC Not Fitted
DDB_ECARD_NOT_FITTED
Ethernet board not fitted
357
NIC No Response
DDB_NIC_NOT_RESPONDING
Ethernet board not responding
358
NIC Fatal Error
DDB_NIC_FATAL_ERROR
Ethernet board unrecoverable error
359
NIC Soft. Reload
DDB_NIC_SOFTWARE_RELOAD
Ethernet problem
360
Bad TCP/IP Cfg.
DDB_INVALID_NIC_TCPIP_CONFIG
Ethernet problem
361
Bad OSI Config.
DDB_INVALID_NIC_OSI_CONFIG
Ethernet problem
362
NIC Link Fail
DDB_NIC_LINK_FAIL
Ethernet link lost
363
NIC SW Mis-Match
DDB_SW_MISMATCH_ALARM
Ethernet board software not compatible with main CPU
364
IP Addr Conflict
DDB_NIC_IP_ADDRESS_CONFLICT
The IP address of the IED is already used by another IED
365
IM Loopback
DDB_INTERMICOM_LOOPBACK
EIA(RS)232 InterMiCOM indication that Loopback testing is in progress
366
IM Message Fail
DDB_INTERMICOM_MESSAGE
EIA(RS)232 InterMiCOM Message Failure alarm. Setting that is used to alarm for poor channel quality. If during the fixed 1.6 s rolling window
the ratio of invalid messages to the total number of messages that should be received (based upon the ‘Baud Rate’ setting) exceeds the
above threshold, a ‘Message Fail’ alarm will be issued
367
IM Data CD Fail
DDB_INTERMICOM_DCD
EIA(RS)232 InterMiCOM Data Channel Detect Fail i.e. modem failure
368
IM Channel Fail
DDB_INTERMICOM_CHANNEL