EasyManua.ls Logo

GE P54E - Page 812

GE P54E
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix B - Settings and Signals
P54A/B/C/E
B246
P54xMED-TM-EN-1
ORDINAL SIGNAL NAME ELEMENT NAME
DESCRIPTION
VT supervision slow block - blocks elements which would otherwise maloperate some time after a fuse failure event occurs
834
Bfail1 Trip 3ph
DDB_CBF1_TRIP_3PH
Three phase output from circuit breaker failure logic, stage 1
835
Bfail2 Trip 3ph
DDB_CBF2_TRIP_3PH
Three phase output from circuit breaker failure logic, stage 2
838
Control Trip
DDB_CONTROL_TRIP
Control trip - operator trip instruction to the circuit breaker, via menu, or SCADA. (Does not operate for protection element trips)
839
Control Close
DDB_CONTROL_CLOSE
Control close command to the circuit breaker. Operates for a manual close command (menu, SCADA), and additionally is driven by the auto-
reclose close command
842
Close in Prog
DDB_CONTROL_CLOSE_IN_PROGRESS
Control close in progress - the relay has been given an instruction to close the circuit breaker, but the manual close timer delay has not yet
finished timing out
844
AR 3pole in prog
DDB_AR_3_POLE_IN_PROGRESS
Auto Reclose 3 pole in Progress
845
AR 1pole in prog
DDB_AR_1_POLE_IN_PROGRESS
Auto Reclose AR 1 pole in Progress
846
Seq Counter = 0
DDB_SEQ_COUNT_0
Sequence Counter = 0
847
Seq Counter = 1
DDB_SEQ_COUNT_1
Sequence Counter = 1
848
Seq Counter = 2
DDB_SEQ_COUNT_2
Sequence Counter = 2
849
Seq Counter = 3
DDB_SEQ_COUNT_3
Sequence Counter = 3
850
Seq Counter = 4
DDB_SEQ_COUNT_4
Sequence Counter = 4
851
Seq Counter > 4
DDB_SEQ_COUNT_5
Sequence Counter > 4
852
CB Succ 3P AR
DDB_AR_SUCCESSFUL_RECLOSE
This signal is set when CB has successfully completed a three phase autoreclose cycle.
853
3P Dead Time IP
DDB_DEAD_TIME_IN_PROGRESS
Three pole dead time in progress
854
Auto Close
DDB_AUTO_CLOSE
This is a signal issued by the autoreclose logic to the general CB Control logic when the conditions to autoreclose CB are satisfied (dead time
complete, CB healthy etc).
858
AR Force 3 pole
DDB_AR_FORCE_3_POLE_TRIPS
Used by in-built Trip conversion logic to allow AR to convert CB to 3pole tripping
859
AR Blocked
DDB_AR_BLOCKED
Indicates that AR is in one of the following states, Disabled, Inhibited, AR In Progress or Locked out
860
Lockout Alarm
DDB_CB_LOCKOUT_ALARM
Composite lockout alarm - circuit breaker locked out due to auto-recloser, or condition monitoring reasons
862
Block Contacts
DDB_CONTACTS_BLOCKED_IP
DDB to block output contacts, same as setting Commissioning Column -> Test Mode -> Contacts Blocked
863
Contacts Blocked
DDB_CONTACTS_BLOCKED_OP
Indicates contacts blocked mode enabled. Can be mapped in PSL and sent via InterMiCOM/IM64 to block contacts at the remote end.
864
IA< Start
DDB_PHASE_A_UNDERCURRENT
A phase undercurrent level detector pickup (detects low current). It is used for breaker failure and for fault record reset.
865
IB< Start
DDB_PHASE_B_UNDERCURRENT
B phase undercurrent level detector pickup (detects low current). It is used for breaker failure and for fault record reset.
866
IC< Start
DDB_PHASE_C_UNDERCURRENT
C phase undercurrent level detector pickup (detects low current). It is used for breaker failure and for fault record reset.
873
ISEF< Start
DDB_SEF_UNDERCURRENT
SEF undercurrent level detector pickup (detects low current in CT SEF)
874
CBF Non I Trip
DDB_CBF_NON_I_TRIP
Mapped in PSL to all none current protection trip signals to initiate CB Fail
877
TOC Active
DDB_TOC_ACTIVE
Trip on close functions (either SOTF or TOR) active. These elements are in-service for a period of time following circuit breaker closure

Table of Contents

Related product manuals