Loading...
OUTDOOR
EQUIPMENT
WITH
PROTECTED
AISLE
13
.
Anchor
the
base
of
the
protected
aisle
assembly
to
the
concrete
pad
using
the
anchor
clips
provided
.
Install
anchor
bolts
in
accordance
with
the
requisition
drawing
.
1
.
Remove
aisle
front
wall
from
the
front
of
the
metal
-
clad
switchgear
equipment
,
discard
all
yellow
shipping
covers
on
aisle
Wall
and
front
of
metal
-
clad
equipment
except
lifting
members
.
Re
-
use
3
/
8
-
16
hardware
.
See
Fig
.
16.1
,
details
S
-
T
,
U
-
V
,
W
-
X
.
Since
the
relay
and
in
-
strument
cases
are
not
weatherproof
,
the
control
panels
should
be
protected
from
inclement
weather
until
the
installation
of
the
aisle
enclosure
is
completed
.
2
.
Lay
down
aisle
floor
in
front
of
each
metal
-
clad
unit
(
Fig
.
16.4
)
.
Secure
at
each
unit
line
with
tie
plate
and
floor
cap
per
detail
A
-
B
.
Secure
to
metal
-
clad
per
detail
E
-
F
.
m
OUTDOOR
EQUIPMENT
WITH
COMMON
AISLE
1
.
Remove
and
discard
the
yellow
shipping
covers
on
front
of
metal
-
clad
equipment
.
Since
the
relay
and
in
-
strument
cases
are
not
weatherproof
,
the
control
panel
should
be
protected
from
inclement
weather
until
the
installation
of
the
aisle
enclosure
is
completed
.
2
.
Lay
down
aisle
floor
in
front
of
each
metal
-
clad
unit
of
first
switchgear
line
-
up
.
Secure
to
metal
-
clad
per
detail
E
-
F
.
3
.
Move
second
switchgear
line
-
up
into
position
and
secure
to
aisle
floor
per
detail
E
-
F
.
After
the
switchgear
is
secured
to
the
aisle
floor
,
it
should
be
anchored
to
the
concrete
pad
using
the
anchor
clips
provided
.
Install
anchor
bolts
in
accordance
with
the
requisition
drawing
.
4
.
For
aisle
end
wall
design
,
disassemble
channel
cap
,
cap
bushing
,
roof
cap
,
end
trim
and
corner
cap
(
Fig
.
16.3
)
.
Reassemble
at
end
of
aisle
that
has
the
aisle
end
wall
.
Re
-
use
1
/
4
-
20
hardward
and
plug
buttons
.
Fig
.
16.8
and
detail
EE
-
FF
.
5
.
Disassembe
aisle
end
extensions
(
Fig
.
16.2
,
detail
Y
-
Z
)
or
aisle
end
extension
and
aisle
end
wall
.
Fig
.
15.3
,
detail
A
A
&
BB
.
Do
not
remove
shipping
support
from
aisle
end
wall
.
3
.
For
aisle
end
wall
design
,
disassemble
channel
cap
,
cap
bushing
,
roof
cap
,
end
trim
and
corner
cap
(
Fig
.
16.3
)
.
Reassemble
at
end
of
aisle
that
has
the
aisle
end
wall
.
Re
-
use
1
/
4
-
20
hardware
and
plug
buttons
.
Fig
.
16.8
and
detail
EE
-
FF
.
4
.
Disassemble
aisle
end
extensions
(
Fig
.
16.2
,
detail
Y
-
Z
)
or
aisle
end
extension
and
aisle
end
wall
.
Fig
.
16.3
,
detail
BB
&
AA
.
Do
not
remove
shipping
support
from
aisle
end
wall
.
5
.
Position
aisle
end
extension
(
s
)
and
/
or
aisle
end
wall
(
s
)
at
ends
of
the
line
up
.
Secure
aisle
extension
to
aisle
floor
and
metal
-
clad
Fig
.
16.5
,
detail
A
-
B
,
H
-
G
.
Secure
aisle
end
wall
per
detail
AA
-
BB
.
6
.
Set
up
aisle
wall
and
secure
to
aisle
floor
,
aisle
end
extension
(
s
)
,
aisle
end
wall
(
s
)
and
shipping
split
.
Fig
-
ures
16.4
,
16.5
,
16.6
details
J
-
K
,
C
-
D
,
AA
-
BB
.
7
.
Apply
prestite
gasketing
material
to
top
of
aisle
wall
(
Fig
.
16.6
)
,
metal
-
clad
roof
(
Fig
.
16.7
)
,
and
aisle
end
wall
(
Fig
.
16.9
)
.
Punch
holes
in
gasket
with
drift
pin
.
8
.
Remove
roof
angle
(
re
-
use
1
/
4
-
20
hardware
)
and
set
aisle
roofs
in
place
,
taking
care
to
align
the
lap
joint
be
-
tween
the
aisle
and
switchgear
roof
assemblies
before
contacting
prestite
gasket
.
Secure
roof
sections
to
each
other
,
to
aisle
wall
and
to
metal
-
clad
per
Figures
16.6
and
16.7
,
details
R
,
L
-
M
and
P
-
N
.
9
.
Apply
RTV
clear
seal
and
assemble
roof
caps
,
cap
bush
-
ings
and
channel
end
caps
.
Fig
.
16.8
details
L
-
M
,
P
-
N
.
10
.
After
steel
erection
is
complete
,
check
to
certify
that
all
bolted
,
butt
or
overlapped
joints
are
resistant
to
water
leaks
.
A
source
of
outside
light
in
a
darkened
aisle
is
an
indication
that
RTV
108
clear
seal
should
be
applied
to
the
exterior
surfaces
.
6
.
Position
aisle
end
extensions
)
and
/
or
aisle
end
wall
(
s
)
at
ends
of
the
line
-
up
.
Secure
aisle
extension
to
aisle
floor
and
metal
-
clad
Fig
.
16.5
,
detail
A
-
B
,
H
-
G
.
Secure
aisle
end
wall
per
detail
AA
-
BB
.
7
.
Apply
prestite
gasketing
material
to
top
of
metal
-
clad
roof
(
Fig
.
16.7
)
,
and
aisle
end
wall
(
Fig
.
16.9
)
.
Punch
holes
in
gasket
with
drift
pin
.
8
.
Remove
roof
angle
(
re
-
use
1
/
4
-
20
hardware
)
and
set
aisle
roofs
in
place
taking
care
to
align
the
lap
joint
between
the
aisle
and
switchgear
roof
assemblies
be
-
fore
contacting
prestite
gasket
.
Secure
roof
sections
to
each
other
and
to
metal
-
clad
per
Figures
16.6
and
16.7
,
details
R
,
L
-
M
,
and
P
-
N
.
9
.
Apply
RTV
clear
seal
and
assemble
roof
caps
,
cap
bushing
and
channel
end
caps
.
Fig
.
16.8
,
details
L
-
M
,
P
-
N
.
10
.
After
steel
erection
is
complete
,
check
to
certify
that
all
bolted
,
butt
or
overlapped
joints
are
resistant
to
water
leaks
.
A
source
of
outside
light
in
a
darkened
aisle
is
an
indication
that
RTV
108
clear
seal
should
be
applied
to
the
exterior
surfaces
.
11
.
Assemble
Hayco
grommets
in
the
aisle
roof
sections
.
11
.
Assemble
Hayco
grommets
in
the
aisle
roof
sections
.
12
.
Assemble
and
wire
the
light
switches
,
receptacles
,
lamp
sockets
,
etc
.
in
accordance
with
the
wiring
diagrams
furnished
for
the
equipment
.
»
25
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals